background image

5 OM-ECOARCH

START/CHECK/BALANCE

DIRECT DRAW HOODS

1.   Close all doors and windows.
2.   Operate all exhaust fans, even fans serving other hoods, make-up air units 

and building HVAC.

3.   Turn on all cooking equipment under the hood to preheat to operating 

temperature.

4.   Produce large quantities of smoke.
5.   Observe capture of vapors.
6.   If all vapors are not captured, increase exhaust fan RPM.
7.   Check air pressure in kitchen. Pressure must be negative relative to dining 

room pressure.

8.   Air velocities entering the kitchen from the dining room should not exceed 

100 FPM. 

 

No air should be moving toward the dining area.

9.   Repeat steps 6 and 7 until all vapors are captured.
10.  Same as step 7 with bottom of next section.
NOTE: The exhaust and supply (if any) air flow rates were established under 
controlled laboratory conditions, and greater exhaust and/or lesser supply air 
may be required for complete vapor and smoke removal in specific installations.

MAKE-UP AIR HOODS EXHAUST FAN(S)

1.   Open all doors and/or windows leading to outside.
2.   Start the exhaust fan only. Do not run the supply fan or make-up unit.
3.   Refer to drawings and/or UL information label on hood for proper CFM 

requirements.

4.   Adjust speed of exhaust fan to obtain proper air velocities and CFM through 

grease filters.

Final Balance

1.   Close all doors and windows.
2.   Operate all exhaust fans even those serving other hoods, supply fans, make-

up air unit and building HVAC system.

3.   Turn on all cooking equipment under the hood and preheat to operating 

temperature.

4.   Produce large quantities of smoke or steam.
5.   Observe capture of vapors.
6.   If all vapors are not totally captured, fine tune the system by adjusting the 

air volume control damper installed in the supply collar. Slightly reduce the 
amount of supply air directed under the hood until full capture is obtained.

SUPPLY FAN OR MAKE-UP AIR UNIT

1.   Start the supply fan and/or make-up unit only. Do not run the exhaust fan. 
2.  Refer to drawings or UL information label on hood for proper CFM 

requirements.

PERIODIC MAINTENANCE

WARNING:  ELECTRICAL SHOCK HAZARD! DISCONNECT POWER BEFORE SERVICING.  

REPLACE ALL PARTS AND PANELS BEFORE OPERATING. FAILURE TO DO 

SO CAN RESULT IN DEATH OR ELECTRICAL SHOCK.

CAUTION:  MAKE SURE ALL COOKING EQUIPMENT, THE EXHAUST HOOD AND UVC 

EXHAUST AIR CLEANER HAVE BEEN TURNED OFF AND ALLOWED TO COOL. 

HOT EQUIPMENT CAN CAUSE BURNS.

CAUTION:  USE STEP LADDER OR OTHER STABLE PLATFORM TO PROVIDE EASY 

ACCESS TO THE INTERIOR OR THE UVC LAMP CABINET. DO NOT STAND ON 

COOKING EQUIPMENT TO SERVICE THE UVC. FALLS CAN CAUSE SERIOUS 

INJURIES.

BAFFLE FILTERS

Filters should be removed and cleaned at least weekly, depending on hours of 
operation. Filters may be cleaned by soaking in a strong detergent solution or 
running thru a dishwasher. When replacing, make sure filters and handles are 
running vertically, and filters are seated properly.

MODULAR GREASE EXTRACTORS

Modules should be removed and cleaned at least weekly, depending on hours of 
operation. Modules may be cleaned with a brush and a strong detergent solution 
or run thru the dishwasher. When replacing modules, make sure they are seated 
properly.

GREASE TROUGH

Should be checked weekly for grease build up and cleaned with strong detergent 
if necessary.

GREASE COLLECTION RECEPTACLE

Should be emptied at least once a day and cleaned daily with a strong detergent.

HOOD CANOPY

Inside hood canopy should be wiped down as needed. The area at the exhaust 
intake openings should be wiped down daily.
Inspect inside of extraction chamber at least weekly to insure proper cleaning 
and that the trough and access door are free of foreign matter.

UV PREVENTATIVE MAINTENANCE 

Clean the UV lamp at the same time the grease extractors are being cleaned (or 
daily), wipe down the UV lamp exterior using a dry towel and a non-detergent 
cleaning agent such as sanitizing solution or white vinegar. 
IMPORTANT: Do not allow cleaner to run into lamp fittings or socket enclosures.
IMPORTANT: UV System will not work properly without daily cleaning of the UV 
lamp.

Summary of Contents for Unified Brands Avtec EcoArch

Page 1: ...r extinguishing systems may be factory supplied ULTRAVIOLET UV SERIES The EcoArch Energy Efficient Ventilation UVc is a door assembly integrally installed in the exhaust plenum of an EcoArch canopy consisting of UVc filtration system designed for use in the ventilation control of commercial cooking operations of listed hood systems A depiction of this unit is indicated at left The UVc filtration s...

Page 2: ... VOLUME CONTROL DAMPER FLUID WELD Installation Instructions LT D D Avtec hoods are provided with adjustable hanging brackets designed to receive 1 2 threaded rod with a 1 2 nut and washer Supporting rods must be connected to all factory installed brackets Recommended hanging height is 6 6 above finished floor for canopies Low side wall ventilators should be installed directly upon a Avtec base or ...

Page 3: ...The exhaust fan curb should be installed directly above the hood if possible Always maintain the shortest duct run possible 4 Cut hole and seal exhaust fan curb to roof 5 Duct shall be sized to provide air velocities not exceeding 1200 FPM 6 Install hinges and airline cable on exhaust fan cap and metal curb Remember to leave ample room for fan to tilt back Fan will remain in tilted back position 7...

Page 4: ...he outside of the hood Bolts and acorn nuts should be attached per the drawing stainless bolts and acorn nuts supplied 3 Skirt flange should be screwed to the wall screws not provided TOP ENCLOSURES Enclosure panels are provided for exposed side s of hood s 1 Hoods ordered with enclosure panels will be shipped with clips installed on perimeter of hood top where panels are to be installed 2 Slide e...

Page 5: ...ot run the exhaust fan 2 Refer to drawings or UL information label on hood for proper CFM requirements PERIODIC MAINTENANCE WARNING ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING REPLACE ALL PARTS AND PANELS BEFORE OPERATING FAILURE TO DO SO CAN RESULT IN DEATH OR ELECTRICAL SHOCK CAUTION MAKE SURE ALL COOKING EQUIPMENT THE EXHAUST HOOD AND UVC EXHAUST AIR CLEANER HAVE BEEN TURNED OFF A...

Page 6: ... there has been a breach of warranty by UNIFIED BRANDS must give us written notice within THIRTY 30 days after discovery of the relevant defect or the right to assert such claim will have been waived conclusively and provided further that any such claim must also be asserted within the general warranty period for such equipment and or parts UNIFIED BRANDS will not be liable for any expense incurre...

Page 7: ...7 OM ECOARCH Wiring Diagram RELAY BOX BALLAST BOX ...

Page 8: ...8 OM ECOARCH Wiring Diagram ...

Page 9: ...9 OM ECOARCH Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By ...

Reviews: