12
Installation • Software Provisioning
2.4
Software Provisioning
For front panel craft port configuration, see section 2.4.1. For Web Browser configuration via LAN, see section
2.5.
2.4.1 Front panel craft port configuration
Once the Net Guardian Expansion is connected to the Net Guardian 832A, the Net Guardian 832A must be con-
figured to access the Net Guardian Expansion functions. Connect a computer terminal to the front panel craft port
using a standard download cable (DPS part number D-PR-045-10B-04).
1.
Ensure the connecting computer’s settings matches the Net Guardian 832A (9600, N, 8, 1) and
connect a DB9 serial cable to the DB9 connector on the Net Guardian front panel labeled
“CRAFT.”
2.
Open up a terminal emulation program such as HyperTerminal, and connect to the Net Guardian direct to
COM 1 (or whatever COM port you are using).
3.
Type: ‘DPSCFG’ <enter>
4.
The Net Guardian will respond Password:
5.
Type: ‘dpstelecom’ <enter> (Factory default) - or existing password if applicable.
6.
The Net Guardian main menu will appear.
7.
Type ‘C’ for Configure.
8.
Type ‘E’ for Edit.
9.
Type ‘P’ for Port.
10. Type ‘O’ for Options.
11. Select ‘N)GDdx’
12. Enter the number of Net Guardian Expansions installed (e.g. 1, 2, or 3) and press ENTER.
The number of NGDdx units should now reflect the number you just entered.
13. Press ESC twice to back up to the E)dit menu. The Next step is to provision the 48 discrete points for each
Net Guardian Expansion.
Fig. 2.4.1 –
Enter the number of expansion units attached to the Net Guardian.
Password: **********
NetGuardian v1.5D.0099
C)onfig P)roxy D)ebug e(X)it
E)dit M)onitor P)ing S)tats R)eset modem (ESC) ? E
s(Y)stem L)ogin P)orts pa(G)ers A)larms R)elays
a(N)alogs p(I)ng info T)imers D)ate/time n(V)ram (ESC) ? P
E)thernet M)odem C)raft D)ata O)ptions (ESC) ? O
NGDdx Units
: 0
GLD Units
: 0
N)GDdx G)LDs (ESC) ? N
NGDdx Units (0-3) : 2
NGDdx Units
: 2
GLD Units
: 0
N)GDdx G)LDs (ESC) ?
Summary of Contents for D-PC-293-10A
Page 22: ...20 Notes ...