16
Installation • Web Browser Configuration
2.5.2 Edit - Base Alarms
All 48 discrete alarms (per unit) can be configured using this menu. Description of the alarm point, polarity
(nrm/rev), whether to use an SNMP Trap or not; and the primary/secondary pager to use report the alarm are con-
figured in this submenu.
1.
From the Edit menu select “Base Alarms”. (See figure 2.5.2)
2.
Enter a description of each alarm being utilized.
3.
Set the Reverse (polarity). Normal = contact closure is an alarm. If the Reverse option is selected, the alarm is
clear when closed.
4.
Set the Trap. Trap toggles the SNMP information. Selecting the box = Send Trap, leaving the box blank = Don’t
Send. This allows you to designate if an SNMP trap is to be sent when an alarm condition exists.
5.
Set the Primary and Secondary Pagers. This allows you to designate pagers. The Net Guardian 832A will issue
one call to the primary pager device followed by one call to the secondary pager device. Enter a pager ID from
the pager list.
Note:
The pager device can be an ASCII terminal, T/MonXM element manager or IAM element manager, E-mail, or multi-
ple SNMP managers as well as an alpha or numeric pager.
Fig. 2.5.2 -
Configure the 48 discrete alarms (per unit) from the Base Alarms screen.
Select
the Base
Alarms
screen