Issue 6 – December 2006
10
0.50
- 0.5
-Ur-
-Or-
Display board
The display shows the gas level, or indicates that the gas level exceeds the
measuring range (over-range) or is below the measuring range (under-range).
Examples
Normal gas level display.
Negative display reading. A negative display reading
may be caused by inaccurate calibration or by drift or
temperature effect of the sensor.
Under-range: reading below measuring range
Over-range: reading above measuring range. The
over-range indication is latching and can only be
cleared when the reading is again within the
measuring range. Press Reset to clear the over-
range indication.
There are two versions of the display board:
x
V1 displays gas level, under-range and over-range, and calculates a TWA gas
level over eight hours; this board contains firmware release 1.00 or 1.01.
x
V2 displays gas level, under-range and over-range and calculates the TWA
gas level over an user-adjustable period, and logs the gas level to memory;
this board contains firmware release 2.00 or 2.01.
The firmware version is shown on the display for a few seconds after the unit is
turned on, and is also marked on the display board.
A buzzer on the display board provides a local audible alarm.
Display of measuring range, gas and unit
The front cover of the controller has a window in which to display the measured gas,
range and unit. Insert a label showing the required information in the slot inside of the
front cover. Pre-printed and blank labels are at the end of this manual.
Summary of Contents for REGARD-1
Page 38: ...Issue 6 December 2006 38 EC type examination certificate ...
Page 39: ...Issue 6 December 2006 39 ...
Page 40: ...Issue 6 December 2006 40 ...
Page 41: ...Issue 6 December 2006 41 ...
Page 44: ...Issue 6 December 2006 44 ...
Page 46: ...Issue 6 December 2006 46 ...
Page 47: ...Issue 6 December 2006 47 ...