background image

Limit Switch Adjustments 

CAUTION:

 

Be sure all switches are in “off” position before adjusting limit switches 

Always be prepared to shut lift off manually when new adjustment is being tested.

Limit switches for the AeroLift 35 are preset at the factory. The “Up” (closed) limit switch 

is set for fully closed. The “down” (show) limit switch is set for fully lowered. Once unit is 

in place, the “down” limit switch may need to be changed to stop the AeroLift 35 closer 

to the ceiling (that is, to raise the “down” position). Limit switches are located on the end 

of roller, and are accessible by removing the cover of the junction box at the left end of 

the unit. To adjust the limit switches, use a 

5

/

32

" screwdriver/allen wrench. 

 

Caution: It is not uncommon to overheat the motor during initial installation 

when setting limits. The motor is thermally protected and will stop working until it 

has cooled to a safe temperature before it will start operating again. DO NOT 

physically pull the unit down when this occurs.   

Adjusting “Down” 

(SHOW position) 

“Down” position may be adjusted by turning the #1 limit switch adjustment socket. Turning 

the socket clockwise will stop the AeroLift 35 closer to the ceiling. Turning it counter-

clockwise will cause the lift to stop at a lower point.

Adjusting “Up” 

(CLOSED position) 

Because the “up” (“closed”) position is preset at the factory, Draper does not recommend 

changing this position using the limit switch. The “up” position of the closure may be 

changed by changing the length of threaded rod (see fig. 6). If necessary, however, 

“up” position may be adjusted by turning the #2 limit switch adjustment socket. Turning 

the socket counterclockwise creates a higher, or more fully closed position. Turning it 

clockwise creates a lower ‘UP” (closed) position.

Caution: Make sure limit switch is set so that the AeroLift 35 motor is NOT still 

running after the lift is closed. If it continues to cycle once the lift is closed, a 

failure may occur, making the unit descend rapidly and causing damage and/or 

injury.

Please Note: 

If load is off-center of pan, you may need to adjust the pitch of the 

fabric rollers. One setscrew is provided on each end of both fabric rollers (see 

above drawing). Use these to adjust roller pitch to keep entire fabric panel taut, so 

load is evenly distributed. Use 3mm hex key to adjust.

Operation

When unit is first operated, be cautious! If unit fails to operate when the switch 

is flipped “down”, return switch to “off” and re-check electrical connections 

before proceeding. Cycle unit down and up several times to confirm satisfactory 

operation.

 

220V Single Station Control 

3-position up-off-down switch permits operation to be stopped at any point. Factory 

adjusted limit switches automatically stop AeroLift when fully down or fully up.

Optional 220V Multiple Station Control

Switches are similar in appearance to 220V Single Station Control. AeroLift stops 

when switch is released and may be restarted in either direction. Factory adjusted 

limit switches automatically stop AeroLift when up or fully down.

Optional 24V Control

Three-button up-stop-down switches stop at any point desired, operate in any 

sequence. Factory adjusted limit switches automatically stop AeroLift when fully up 

or fully down.

Optional Infrared or Radio Frequency Remote Control

If ordered, a three-button transmitter is provided, with “up”, “down” and “stop” 

buttons. Unit starts up or down when appropriate button is pressed, and may be 

stopped by pressing “off” button. Factory set limit switches stop unit automatically 

when projector is in “show” position. Multiple Station Control required for this 

option.

Optional RS232/Ethernet

Serial communication and network communication optionally available with wall 

switches, RF or IR remote.

Optional Key Operated Switching 

Two kinds of key-operated switches are optionally available with this unit.   

The key-operated power supply switch controls power to the AeroLift 35 and 

switches. When it is “off”, the switches will not operate lift. Key may be removed 

from the switch in either “on” or “off” position.   

A three-position key switch permits the AeroLift 35 to be operated directly by key. 

In this case, the screen’s operator must always have a key.

AeroLift 35 

(220V)

 by Draper, Inc.

 

page 2 of 4

Testing the Safety Limit Switches

The AeroLift 35 are equipped with two Safety Limit Switches 

(see 

"AeroLift— 

Limit Switch Adjustment (Bottom View)" 

diagram on page 3).

 These switches 

may be damaged during shipping or by rough handling on the job site.  

 

Once the AeroLift has been installed in the ceiling, but 

before the projector and closure are attached, the Safety 

Limits must be tested.  

Use a screwdriver or other tool to press and hold the limit switch. While hold-

ing down the limit switch, have someone operate the unit. 

If the unit runs up 

while the limit switch is depressed, the limit switch is broken and must be 

replaced

. Operating the unit without a functioning Safety Limit Switch could cause 

the unit's motor to continue operating after the lift is closed, leading to a failure and 

the possibility of damage or injury. Make sure to test BOTH switches.

Please Note: As weight is applied to the AeroLift, the projector plate may 

shift slightly. If this occurs, use setscrews on bottom of fabric roller brackets 

to compensate for shift and level projector plate (see page 3).

JUNCTION BOX

UP LIMIT

DOWN LIMIT

Fabric Roller Adjustment Setscrew

Figure 

(2)

Electrical Connections

Unit operates on 220V AC current. The AeroLift 35 is shipped closed, with a 

temporary field connection provided in the form of a pigtail temporarily wired 

to the unit. After hanging the unit, make sure power is off and use this pigtail to 

temporarily connect the unit to power and to a switch, so the unit can be lowered 

to allow access inside.

Please note: Make sure electrical supply has been disconnected before 

attempting to connect AeroLift to electricity.

Terminal strip for field connections is located inside a junction box on the end 
of the unit. Unit is shipped with internal wiring complete to the terminal strip. 

Once the unit has been lowered, 

turn off power 

and remove the J-box cover. 

The terminal strip is attached to the cover. Disconnect temporary pigtail from 

unit, then complete permanent wiring to electricity and to switches. Wire to 

connect unit to power supply and to switches should be furnished by installer. 

Connections should be made in accordance with wiring diagram, and wiring 

should comply with national and local electrical codes. All operating switches 

should be “off” before power is connected. AeroLift should be operated and 

checked prior to installing projector and/or optional ceiling closure.

Summary of Contents for AeroLift 35

Page 1: ...r damage 2 Locate the following parts A The unit itself B Controls C Any optional equipment 3 Test lift prior to installation AeroLift 35 with Closure panel Hanging Unit The AeroLift is provided with four 4 mounting angles for suspending or direct mounting the unit from above or direct mounting from the sides These angles provide up to 32mm of adjustment side to side The AeroLift 35 is designed to...

Page 2: ... fully down Optional Infrared or Radio Frequency Remote Control If ordered a three button transmitter is provided with up down and stop buttons Unit starts up or down when appropriate button is pressed and may be stopped by pressing off button Factory set limit switches stop unit automatically when projector is in show position Multiple Station Control required for this option Optional RS232 Ether...

Page 3: ...the ceiling to allow future access The optional environmental air space housing must be installed to isolate the lift from the other space used for environmental air Includes trim ring for ceiling opening See installation instructions included with Environmental Air Space Housing Installing Optional Ceiling Closure If your AeroLift is equipped with optional ceiling closure it can be used as is or ...

Page 4: ...required if both are used with one Lift LVC 3 Button Wall Switch DOWN Black COM White UP Red AeroLift Terminal Block UP N N DN COM Wiring Diagrams Single Station Control To 220 240 Vac Line Dashed Wiring By electrician LS2 LS1 LS2 LS1 BK BL BL BRN OR RD 1 2 3 4 5 6 7 8 TB BK RD BK BK BK BL WH GN YL 14 AWG GN YL RD 14 AWG BK 14 AWG WH 14 AWG GN14 AWG BK 14 AWG BK PROJECTOR OUTLET MOTOR BRN BL L1 N ...

Reviews: