220 V Revelation by Draper 

Page 6 of 8

Field Installation of Environmental Airspace Housing Kit

       

Caution! Disconnect power from the Revelation before installing Envi-
ronmental Airspace Housing.

1

   Remove the covers from the electrical chassis in the Revelation.

2

   Disconnect the black 14 awg. wire that runs from the T2 transformer to 

the receptacle in the electrical chassis.

3

   Install the pre-wired current sensor using two #6-32 x 1" [10] long screws 

provided. (SEE FIGURE #1.)

4

   Connect each wire of the pre-wired current sensor as shown by DIA-

GRAM #1.

5

  Install the two fan mount assemblies [5,6] to the main pan of the Rev-

elation using the eight #10-32 x .

3

/

8

" [7,8] long screws provided. (SEE 

FIGURE #1.) Attach the long leads of the Exhaust Fan Assembly [6] to 
the end with the motor and lifting mechanism.

6

   Using the wire clips [11] provided, lay in the wires from the fans as 

shown in FIGURE #1 and connect the fans to TB1-8 & TB1-9 as shown 
in DIAGRAM #1.

7

   Replace the covers to the electrical chassis.

8

   Apply the 25 mm wide Nylon [12,13] tape as shown in FIGURE #1.

9

   Install the inner and outer plenum covers [1,2], and attach the mating 

end panel [3,4] as shown in FIGURE #2.

10

  Fan mounting panels are designed to accept a standard 4" round duct. 

The exhaust flange is located on the motor/drive end of the Revelation 
and the input is located at projector end of the Revelation. 

If duct work is connected to this unit, here are a few recommended guidelines 
you should keep in mind when installing the duct work:

•  Air supply to the Environmental Airspace Housing should be cool enough 

to provide adequate cooling for your projector.

•  Do not obstruct airflow through duct work. Inadequate airflow may result in 

excessive heat buildup inside the unit.

•   Keep duct work length as short as possible. Recommended maximum total 

duct length is 914  cm (input plus exhaust).

•  Keep the input-to-exhaust length ratio balanced and as small as possible 

 

to prevent air from being pushed into or drawn out of the room.

FIGURE #1

DIAGRAM #1

FIGURE #2

ENVIRONMENTAL AIRSPACE HOUSING

INSTALLATION PART LIST

  ITEM# DESCRIPTION 

 

QTY

 

1  INNER ENVIRONMENTAL AIRSPACE HOUSING COVER 

1

 

2  OUTER ENVIRONMENTAL AIRSPACE HOUSING COVER  1

 

3  INNER END PANEL 

 

1

 

4  OUTER END PANEL 

 

1

 

5  INPUT FAN MOUNT ASSEMBLY 

 

1

 

6  EXHAUST FAN MOUNT ASSEMBLY 

 

1

 

7  SCREW #10–32 X .375" (9.525mm) 

 

 

 

HEX HD TYPE "F" ZINC

 

8  WASHER, #10 ZINC INTERNAL LOCK  

 

8

 

9  PRE-WIRED CURRENT SENSOR 

 

1

 

10  SCREW #6–32 X 1" (25.4mm) 

 

 

 

LONG PHIL PAN HD ZINC

 

11  CLIP ADHESIVE BACKED CORD  

 

 

 

6.35mm HOLDING DIA.

 

12  991 mm LONG 25.4mm WIDE X .762mm 

 

 

 

THICK NYLON TAPE

 

13  1092mm LONG 25.4mm WIDE X .762mm  

 

 

 

THICK NYLON TAPE

TOOLS NEEDED

 

 

MED POINT PHILLIP SCREWDRIVER

  

1

/

8

" FLAT BLADE SCREW DRIVER

  

3

/

8

" WRENCH

Nylon tape 43" long

Wire clips typ.

Input 

fan

assembly

(short  

wires)

Curent sensor

TB1

T2

F4

F5

F1

F3

F2

T1

C1

CR2

CR1

TB2

CS1

1                    12

1                    12

1 2  3 4 5

BK

BK

WH

BK RD

1                    10

1                    10

CB1B

CB1A

PCB1

PCB1

Nylon tape 39" long

Projector

Exhaust  

fan

assembly

(long  

wires)

T2 transformer

F1 = 7 Ampere
F2 = 1 Ampere
F3 = 1 Ampere
F4 = 4 Ampere
F5 = 4 Ampere

TB1

Outer Plenum cover

Inner Plenum cover

Inner end panel

Outer end panel

Exhaust

fan

assembly

Input

fan

assembly

Motor

WIRE TO BE REMOVED BEFORE INSTALLING PLENUM WIRING

3. ALL WIRES 18 AWG. UNLESS OTHERWISE SPECIFIED.

WIRES CONNECTED BY INSTALLER

2.

NOTES:

1.

14 AWG

4 TURNS

CS 1

1 2

3 4 5

PCB 1

WH

BK

CB1B

RD

BK

BK

BK

10

9

78

6

BK

35
4

2

1

F2

F1

F3

CB1A

8

10

97

6

BK

3
4
52

1

BK

(IN)

FAN

FAN

(OUT)

BK

YW/GN

7

10

9

8

RD

BE

46

5

3

12

D1

C2

220 VAC SUPPLY

L1

N

12

11

RD

50 - 60 HZ

PROJECTOR 

OUTLET

BE

14 AWG

RD

YW/GN

14 AWG

14 AWG

BE

BE

BE

BE

BE

www.draperinc.com

(765) 987-7999

Summary of Contents for Revelation

Page 1: ...earance of 458mm is required above ceiling level for model B or 347mm for Model A if Environmental Airspace Housing is used If no Environmental Airspace Housing the minimum clearance is 331mm for both models 8 Unit must be installed level use a carpenter s level 9 Unit operates on 220 V a c 60 hz current 10 Please Note The Revelation is not compatible with lenses that have a throw distance of less...

Page 2: ...it must be unobstructed after installation 432mm minimum clearance is required below the door 5 Access should be provided to electrical control box in case service is required 6 Do not use unit to support adjacent light fixtures etc 7 Do not complete the ceiling below unit until electrical connections have been completed and unit has been operated successfully 8 We recommend that safety cables be ...

Page 3: ...ceiling By using the built in adjustment features of the Revelation you should be able to bring the top of the image below the ceiling Adjusting the ceiling closure door may introduce a keystone effect to the image If your projector has a keystone correction feature you may be able to compensate for keystoning Light Path C Single lens projectors with light path geometry C will work with the Reve l...

Page 4: ... Distance approx 432mm approx 432mm Travel Time 9 sec 9 sec Net Weight 39 kg 41 kg Shipping Weight 98 kg 100 kg Projector Space HWL To fit within parameters of inner pan 346mm is overall height of Revelation with Environmental Airspace Housing 330mm WITHOUT Environmental Airspace Housing 6 Mounting holes 9 525mm 3 8 dia Electrical hook up Lens and mirror centerline 462mm Projector 4 4 972 mm 946 m...

Page 5: ...www draperinc com 765 987 7999 YW PCB 1 220 VAC SUPPLY PROJECTOR OUTLET Dashed wiring by Electrician GND N 50 60 HZ L1 14 AWG 14 AWG RD BE YW GN 14 AWG YW GN RD BE F3 CB1B 8 RD 10 9 RD RD RD BK 6 7 4 5 3 2 1 F1 F2 YW YW C2 BK RD BE YW D1 RD DOWN ALL WIRES 18 AWG UNLESS OTHERWISE SPECIFIED BE BK 10 9 8 7 6 5 4 3 2 1 CB1A RD BE BE BE C1 BK RD BE BE BE WH DOWN LIMIT SW UP LIMIT SW RD RD BE BE BE WH B...

Page 6: ...ssive heat buildup inside the unit Keep duct work length as short as possible Recommended maximum total duct length is 914 cm input plus exhaust Keep the input to exhaust length ratio balanced and as small as possible to prevent air from being pushed into or drawn out of the room FIGURE 1 DIAGRAM 1 FIGURE 2 ENVIRONMENTAL AIRSPACE HOUSING INSTALLATION PART LIST ITEM DESCRIPTION QTY 1 INNER ENVIRONM...

Page 7: ...r of the unit Service and maintenance is made simpler due to the accessibility provided by this unique Environmental Airspace Housing design Each Environmental Airspace Housing also features a ventilation system designed to maintain a suitable operating environment for your projector An integrated current sensor in the Revelation circuitry turns on the fans anytime the projector is operating and c...

Page 8: ...ER by rotating it into the limit switch until the limit switch clicks and secure the lever onto the shaft using the 10 32 screw 4 and lock washer 5 supplied with the lever Be sure that the screw on the lever is tightened so that the lever does not twist on the shaft 8 After the VIC 12 7 is installed with the screen run the wiring to the Revelation using the cord strain relief 6 and connect to TB1 ...

Reviews: