13
Instruction ES2007 4/98
Models 4700P and 4700E
Electrical Installation of 4700E
Electrical connections should be made as shown in Figure
12. The terminals will accept wire sizes up to AWG 14.
The loop controller driving the positioner must be capable
of supplying 4-20 mA with an output voltage compliance of
at least 5 volts.
The available output voltage of a current source will be
reduced by loop wiring resistance. This can be checked by
connecting a resistor of value (250 ohms + Loop Resis-
tance) across the output of the controller and verifying that
at 100% controller output 20 mA is obtainable.
CAUTION: Do not use a voltage source to drive the
positioner as it may cause permanent damage.
Figure 12 - Electrical Connections
INTERNAL
GROUND
SIGNAL
CONNECTIONS
EXTERNAL
CONNECTIONS
WARNING: The positioner must be installed in
accordance with local and national codes of prac-
tice in both general purpose and hazardous area
locations. The electrical components are fully
isolated from ground and therefore grounding is
unnecessary for functional purposes. Grounding
may be necessary to conform to installation codes.
The positioner is normally supplied with a
1
/
2
" NPT conduit
entry. (M20 is optional) Internal and external ground
terminals are provided for use if grounding is required.
INTERNAL
GROUND
SIGNAL
CONNECTIONS
EXTERNAL
GROUND
Summary of Contents for Masoneilan 4700E
Page 15: ...15 Instruction ES2007 4 98 Models 4700P and 4700E Figure 14 FM Installation ...
Page 16: ...Instruction ES2007 4 98 Models 4700P and 4700E 16 Figure 15 CSA Installation ...
Page 17: ...17 Instruction ES2007 4 98 Models 4700P and 4700E Figure 16 CENELEC Installation ...
Page 32: ...Instruction ES2007 4 98 Models 4700P and 4700E 32 Figure 20 4700E Rotary Reciprocating ...