10) Assemble the switchgear cubicles up to a residual gap of about 10 mm between the sides by evenly 

tightening of the screws in the base case and the parallel clamps. 
 

11) Place the screws M8x30 into the holes provided, and tighten these hand-tight (see drawing 

HB71553-001 Pos. 5).  

 

 

 

12) Loosen the clamps and put them aside.  

13) Place the delivered distance sheet steels (8) between the sides whereby the grooves grab over the 

screws (see drawing HB71553-001 Pos. 3 and 5).  
 

14) Tighten the switching cubicles with the screws together until the cubicles are close to each other 

without a gap.  
The switching cubicles are connected in the right way, when the cubicle front is gap free.  
 
 
 

Coupling of the Anti-Burst-System

 

 

 

Loosen the screws (1) with hex driver SW5 all the way to the 
stop. 

 

 

Push the slide (2) all the way to the stop on the right.  

Tighten the screws (1) firmly. 

 

 

 
Do not push the screws (1) sideways. 

 

During works under electrical voltage the screw (1) in the blue circle shall not be 
pushed to the left, because the ABS would release. Pushing backwards the slide 
please secure or block the screw, so that a pushing is not possible. 

 

 

 