ULTRA-SORB MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
PLACEMENT IN AN AIR HANDLING UNIT
See placement recommendations in Figure 9-1.
The metal support frame should be anchored to the air handler casing.
Recommended fasteners for mounting the Ultra-sorb to a metal support frame
are 1/4–20 nuts and bolts or #12 self drilling and tapping screws. Due to
the possible forces exerted on this application, DriSteem recommends fastener
spacing not to exceed 6" (150 mm). On larger Ultra-sorb installations, vertical
channels may be required on both the inlet and outlet ends of the humidifier to
provide proper support. See Figure 10-2.
Air flow
Mounting channel (Typ)
Blank-off plate
Side blank-off
Additional mounting support channels
required on larger Ultra-sorb units
Air handler casing
Ultra-sorb overall width
Steam supply
AHU casing
Dispersion tube
Mounting channel (Typ)
Floor drain
Header
Blanked-off area
1" (25 mm) air gap
OM-7850_airhandler
OM-7851
Air handler overall width
Ultra-sorb
overall
height
See Page 15 for trap dimensions.
Ultra-sorb Model
MP, plan view
FIGURE 10-2: VERTICAL CHANNELS INSIDE AN AIR HANDLER
FIGURE 10-1: ULTRA-SORB MODEL MP INSTALLED INSIDE AN AIR HANDLER
Air handler
overall height
Water seal
Air handling unit: Mounting and support