ULTRA-SORB MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Mounting and support
MOUNTING IN A HORIZONTAL DUCT
The Ultra-sorb panel is contained within a mounting frame.
A mounting flange 1½" (38 mm) wide is provided on all four sides of the
unit. The 1½" (38 mm) wide portion of the header enclosure is intended to be
a mounting flange. See Figures 13-1 and 13-2. A matching flange or metal
frame is required on the ductwork for connection to the Ultra-sorb flanges.
The recommended fastener is a #12 x 3/4" self-drilling and tapping screw,
spacing not to exceed 12" (305 mm). If an angle-iron frame is provided on the
duct section, a longer screw may be required.
Ultra-sorb
Mating flanges of duct are attached to header enclosures
Header enclosure
1½"
(38 mm)
Mounting
flange
Mating flanges of duct are
attached to header enclosures
OM-7864
OM-7863
Side view
FIGURE 13-1: ULTRA-SORB MODEL MP
IN DUCT
FIGURE 13-2: ULTRA-SORB MODEL MP
1½" (38 mm)
Mounting
flange
Do not puncture
the header
Note: To ensure proper drainage mount the
panel level or slightly pitched towards the
piping end of the panel.
For duct-mounted units and AHU-
mounted units wider than 72"
(1829 mm) face dimension, attach
bottom edge of duct work (or AHU
blank-off plate)to header cover
with #12 x 3/4" self-drilling and
tapping screws, spacing not to
exceed 12" (305 mm).