10
FLOOR PROTECTOR
Your wood stove should be placed on a non-combustible surface. The floor protector
should be under the stove, eighteen inches beyond the front and eight inches beyond each
side of the fuel loading and ash removal opening. If there is a horizontal section of
chimney connector, the floor protector should go under it and two inches beyond each
side.
The floor protector should exceed the stove as follows:
FRONT
18’’
(460 mm)
SIDES
8’’
(200 mm)
BACK
8’’
(200 mm)