HeatMax II Furnace Installation and Operation Manual
27
- Block the unused outlets with the block-off caps
(B)
and provided screws
(D)
.
FAVOR THE USE RIGID DUCTS BECAUSE THERE ARE LESS RESTRICTIVE TO AIR
FLOW.
- The maximum run of a main duct is 35’ (10.7 m). It must be reduced from 6" (152 mm)
to 5" (127 mm) after 20' (6.1 m) or reduce the main duct by 1" (25 mm) at every two
secondary duct outputs.
- The maximum length of all the main ducts is 180’ (54.9 m).
- The maximum run of a secondary duct is 10’ (3 m).
- The maximum length of all the secondary ducts is 100’ (30 m).
- The finishing grill at the output of a secondary pipe must be made of metal.