HeatPro Furnace Installation and Operation Manual
15
4.1.3 Minimum chimney height
The top of the chimney should be tall enough to be above the air turbulence caused when
wind blows against the house and its roof.
-
The
chimney
must extend at
least 3 ft. (1 m)
above
the
highest point of
contact with the
roof.
-
Extend at least
2
ft.
(61 cm)
higher than any
roof
line
or
obstacle within a
horizontal
distance of 10 ft.
(3 m).
4.2 The connector pipe
Recommended inner diameter : 6" (152 mm).
If an increaser/reducer must be used (max 6" (152 mm) to 7" (178 mm)), it must
be installed as close as possible the chimney.
4.2.1
Best practices and requisites of the installation code
o
Where passage through a wall or partition of combustible construction is
desired, the installation shall conform to CAN/CSA-B365, Installation Code for
Solid-Fuel-Burning Appliances and Equipment;
o
A flue pipe must never pass through a combustible floor or ceiling or through an
attic, roof space, closet or concealed space;
o
Minimum upward slope towards the chimney: 1/4 in/ft. (20 mm/m);
o
The maximum horizontal run is 10’ (3 m). Do not count the starting elbow;
o
All flue pipe joints must be secured with three screws. Failure to secure them to
each other may cause a fire;
Summary of Contents for HEATPRO DF03000
Page 30: ...HeatPro Furnace Installation and Operation Manual 30 ...
Page 62: ...HeatPro Furnace Installation and Operation Manual 62 11 Exploded diagram and parts list ...
Page 68: ...HeatPro Furnace Installation and Operation Manual 68 12 2 1 Technical data HeatPro ...
Page 69: ...HeatPro Furnace Installation and Operation Manual 69 ...