CONNECTING APPLIANCE TO OIL TANK
•
Make sure that the tank outlet is 12" (305 mm) higher than the inlet of the carburetor. (Gravity fed)
•
Use only copper piping to connect tank to appliance.
•
Make sure that there is a small slope on the connection from the tank toward the appliance.
•
A 3" (75 mm) down slope is needed on the tank itself, from the outlet towards the other end of the tank.
•
When the tank is installed outdoors, it is preferable to use oil #1, to avoid viscosity problems.
NOTE :
THE BAROMETRIC TANK SHALL BE LOCATED SO THAT THE TANK WILL NOT BE
EXPOSED TO THE DIRECT RAYS OF THE SUN OR ADJACENT TO ANY SOURCE OF
INTENSE HEAT.
Figure 11 :
APPLIANCE AND OIL TANK CONNECTION