11
4.1 Program Zones and Partitions
Now that you have enrolled the wireless devices, you
should complete all zone programming on the system.
Although the exact programming required varies
depending on which control panel the LCD5501Z32-
900 is connected to, you should check that the
following programming areas are completed correctly
for each wireless zone:
• Enable zones and/or assign zones to one or more
partitions (programming sections [201]-[209]).
• Program the definition for each zone (programming
sections [001]-[004]).
NOTE: WLS906 wireless smoke detectors must be
assigned to zones defined as Delay 24-hr fire
(wireless) [87] or Standard 24-hr fire (wireless) [88]
for proper supervision.
• Enable the wireless zone attribute for each wireless
zone (PC585, PC1565, PC5008, PC5010 v2.0 and
up, PC5015 v2.2 and up only) (programming
sections [101]-[132]).
See your system Installation Manual, for more
information on each of the above programming
sections.
4.2 Enable Receiver Supervision
The control panel will automatically supervise the
receiver via the Keybus one-minute after at least one
device has been enrolled on the module. The system
will generate a General System Supervisory trouble
if the module is removed from the Keybus. If you need
to remove the LCD5501Z32-900 from an existing
system, you will have to disable supervision of the
PC5132.
4.3 Enable Supervision of Wireless
Zones
NOTE (for PC5010 v1.x control panels only): For UL
Listed installation, Double EOL resistors must be ena-
bled in the PC5010 for the wireless zones to be su-
pervised. If normally Closed or Single EOL resistors
are selected the PC5010 will not be able to supervise
the wireless devices. If a wireless device stops
S E C T I O N 4
Other Programming
sending a supervisory signal (the unit stops function-
ing) the panel will not indicate a supervisory trouble
condition unless Double EOL resistors are used. In
addition, all hardwire zones must be wired for Dou-
ble EOL resistors. For more information, refer to your
PC5010 v1.x Installation Manual.
NOTE (PC5010 v2.0 and higher, PC5015 v2.2 and
higher, PC5008, PC1555, PC580 only): For wireless
supervision to work, you must enable the wireless
zone attribute on all wireless zones (sections [101]
to [132], option [8] ON).
NOTE: The RF Jam Detect zone must have the
supervision option disabled.
NOTE: The supervisory option for any panic pendants
enrolled on the system must be OFF. For UL Listed
systems, the wireless zones must be programmed
as supervised.
Wireless Supervisory Window
Each wireless zone (WLS904, WLS905, WLS906,
WLS907 or WLS915) will send a supervisory signal every
12 minutes. If the receiver does not receive a signal
within the time programmed for the
Wireless Supervisory
Window
, it will generate a supervisory fault.
To program the wireless supervisory window:
1. Enter [
✱
][8][Installer Code] to enter Installer
Programming.
2. Enter [804] to enter into Receiver Programming.
3. Enter sections [81].
4. Enter the time period for the supervisory window
(valid entries are 01-24 hours).
5. To exit press [#].
WLS908 Panic Pendant
The panic pendant does not transmit a supervisory
signal. This is so that the user will be able to take it away
from the premise. You must disable wireless supervi-
sion for each zone in which a panic pendant is assigned.