16
S E C T I O N 7
Tro u b l e s h o o t i n g
1. When I enter the 2-digit zone number when
adding a wireless device, the keypad gives me a
long beep.
You cannot enter ESNs unless the LCD5501Z32-900
is properly connected to the Keybus. See section 2
for instructions on setting up and wiring the PC5132
module.
2. I have entered the ESN for the device but
when I violate the device, the zone does not
show open on the keypad.
Check the following:
• Ensure the ESN has been entered correctly
• Ensure that the zone is enabled for the partition (if
partition programming is used).
• Ensure that the wireless zone is not assigned to a
zone used by PC5108 modules.
• Ensure that the zone is programmed for something
other than “Null Operation.” Wireless smoke
detectors must be assigned to zones defined as
type [87] or [88].
3. When I try a module placement test I get no
result or “Bad” results.
Check the following (see sections 5.1 and 5.2 for
more information on testing devices):
• Verify that you are testing the correct zone
• Verify that the correct ESN was entered when the
device was enrolled
• Verify that the device is in range of the
LCD5501Z32-900. Try testing the device in the
same room as the receiver.
• Confirm that the LCD5501Z32-900 is properly
connected to the Keybus.
• Check that you are testing the zone correctly.
• Check that the batteries are working and installed
correctly.
• Look for large metal objects that may be preventing
the signal from reaching the LCD5501Z32-900.
The device must be located where consistent “Good”
results are obtained. If several devices show “Bad”
results, or if panic pendants and wireless keys operate
inconsistently, move the receiver.
4. The LED on the motion detector does not
turn on when I walk in front of the unit.
The LED is for walk test purposes only. See your
WLS904 instruction sheet for walk test instructions.
5. The WLS908 shows a supervisory fault three
hours after I enrolled it.
The WLS908 does not transmit a supervisory signal.
You must disable supervision for the zone the WLS908
is assigned to (see section 4.3).