3
Enter the following at each keypad installed on the
system:
1. Enter Installer Programming by pressing
[*][8][Installer’s Code]
2. Press [000] for Keypad Programming
3. Press [0] for Partition and Slot Assignment
4. Enter a two digit number to specify the partition
and slot assignment.
NOTE: If your system does not have partitions,
enter [1] for the first digit.
1st digit
Enter 0 for Global Keypad
Enter 1 for Partition 1 Keypad
Enter 2 for Partition 2 Keypad
2nd digit
Enter 1 to 8 for Slot Assignment
5. Press the [#] key twice to exit programming.
6. After assigning all keypads, perform a supervisory
reset by entering [*][8][Installer’s Code][902]. The
panel will now supervise all assigned keypads
and enrolled modules on the system.
To review which modules the control
panel is currently supervising:
1. Enter [
✱
][8][Installer’s Code]
2. Enter [903] to display all modules. On the
I N S T A L L A T I O N
LCD5501Z32-900
keypad, 1
1
1
1
1 and 1
1
1
1
17
7
7
7
7 will scroll on
the keypad to indicate that the LCD5501Z32-900 is
present on the system. 1
1
1
1
1 designates the keypad
section, and 17
17
17
17
17 is used to show the receiver
section is also supervised. On the LCD5500Z
keypad, scroll until the module name appears on
the display.
3. To exit press [#].
If both modules do not show on the keypad, one of
the following conditions may be present:
• the keypad is not connected properly to the Keybus
• there is a problem with the Keybus wiring run
• the keypad does not have enough power