background image

WARNING

 

Please Read Carefully

Note to Installers

This warning contains vital information. As the only individual in
contact with system users, it is your responsibility to bring each item
in this warning to the attention of the users of this system.

System Failures

This system has been carefully designed to be as effective as possible.
There are circumstances, however, involving fire, burglary, or other
types of emergencies where it may not provide protection. Any alarm
system of any type may be compromised deliberately or may fail to
operate as expected for a variety of reasons. Some but not all of these
reasons may be:

 Inadequate Installation

A security system must be installed properly in order to provide
adequate protection. Every installation should be evaluated by a se-
curity professional to ensure that all access points and areas are cov-
ered. Locks and latches on windows and doors must be secure and
operate as intended. Windows, doors, walls, ceilings and other build-
ing materials must be of sufficient strength and construction to pro-
vide the level of protection expected. A reevaluation must be done
during and after any construction activity. An evaluation by the fire
and/or police department is highly recommended if this service is
available.

 Criminal Knowledge

This system contains security features which were known to be ef-
fective at the time of manufacture. It is possible for persons with
criminal intent to develop techniques which reduce the effective-
ness of these features. It is important that a security system be re-
viewed periodically to ensure that its features remain effective and
that it be updated or replaced if it is found that it does not provide
the protection expected.

 Access by Intruders

Intruders may enter through an unprotected access point, circumvent
a sensing device, evade detection by moving through an area of insuf-
ficient coverage, disconnect a warning device, or interfere with or
prevent the proper operation of the system.

 Power Failure

Control units, intrusion detectors, smoke detectors and many other
security devices require an adequate power supply for proper opera-
tion.  If a device operates from batteries, it is possible for the batteries
to fail. Even if the batteries have not failed, they must be charged, in
good condition and installed correctly. If a device operates only by
AC power, any interruption, however brief, will render that device
inoperative while it does not have power. Power interruptions of any
length are often accompanied by voltage fluctuations which may dam-
age electronic equipment such as a security system. After a power
interruption has occurred, immediately conduct a complete system
test to ensure that the system operates as intended.

 Failure of Replaceable Batteries

This system’s wireless transmitters have been designed to provide
several years of battery life under normal conditions. The expected
battery life is a function of the device environment, usage and type.
Ambient conditions such as high humidity, high or low temperatures,
or large temperature fluctuations may reduce the expected battery life.
While each transmitting device has a low battery monitor which iden-
tifies when the batteries need to be replaced, this monitor may fail to
operate as expected. Regular testing and maintenance will keep the
system in good operating condition.

 Compromise of Radio Frequency (Wireless) Devices

Signals may not reach the receiver under all circumstances which could
include metal objects placed on or near the radio path or deliberate
jamming or other inadvertent radio signal interference.

 System Users

A user may not be able to operate a panic or emergency switch possi-
bly due to permanent or temporary physical disability, inability to
reach the device in time, or unfamiliarity with the correct operation. It
is important that all system users be trained in the correct operation of
the alarm system and that they know how to respond when the system
indicates an alarm.

 Smoke Detectors

Smoke detectors that are a part of this system may not properly alert
occupants of a fire for a number of reasons, some of which follow.
The smoke detectors may have been improperly installed or posi-

tioned. Smoke may not be able to reach the smoke detectors, such
as when the fire is in a chimney, walls or roofs, or on the other side
of closed doors. Smoke detectors may not detect smoke from fires
on another level of the residence or building.
Every fire is different in the amount of smoke produced and the
rate of burning. Smoke detectors cannot sense all types of fires
equally well. Smoke detectors may not  provide timely warning of
fires caused by carelessness or safety hazards such as smoking in
bed, violent explosions, escaping gas, improper storage of flam-
mable materials, overloaded electrical circuits, children playing
with matches or arson.
Even if the smoke detector operates as intended, there may be circum-
stances when there is insufficient warning to allow all occupants to
escape in time to avoid injury or death.

 Motion Detectors

Motion detectors can only detect motion within the designated areas
as shown in their respective installation instructions. They cannot dis-
criminate between intruders and intended occupants. Motion detec-
tors do not provide volumetric area protection. They have multiple
beams of detection and motion can only be detected in unobstructed
areas covered by these beams.  They cannot detect motion which oc-
curs behind walls, ceilings, floor, closed doors, glass partitions, glass
doors or windows. Any type of tampering whether intentional or un-
intentional such as masking, painting, or spraying of any material on
the lenses, mirrors, windows or any other part of the detection system
will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in tem-
perature. However their effectiveness can be reduced when the ambi-
ent temperature rises near or above body temperature or if there are
intentional or unintentional sources of heat in or near the detection
area. Some of these heat sources could be heaters, radiators, stoves,
barbeques, fireplaces, sunlight, steam vents, lighting and so on.

 Warning Devices

Warning devices such as sirens, bells, horns, or strobes may not warn
people or waken someone sleeping if there is an intervening wall or
door. If warning devices are located on a different level of the resi-
dence or premise, then it is less likely that the occupants will be alerted
or awakened.  Audible warning devices may be interfered with by
other noise sources such as stereos, radios, televisions, air condition-
ers or other appliances, or passing traffic. Audible warning devices,
however loud, may not be heard by a hearing-impaired person.

 Telephone Lines

If telephone lines are used to transmit alarms, they may be out of
service or busy for certain periods of time. Also an intruder may cut
the telephone line or defeat its operation by more sophisticated means
which may be difficult to detect.

 Insufficient Time

There may be circumstances when the system will operate as intended,
yet the occupants will not be protected from the emergency due to
their inability to  respond to the warnings in a timely manner. If the
system is monitored, the response may not occur in time to protect the
occupants or their belongings.

 Component Failure

Although every effort has been made to make this system as reliable
as possible, the system may fail to function as intended due to the
failure of a component.

 Inadequate Testing

Most problems that would prevent an alarm system from operating as
intended can be found by regular testing and maintenance. The com-
plete system should be tested weekly and immediately after a break-
in, an attempted break-in, a fire, a storm, an earthquake, an accident,
or any kind of construction activity inside or outside the premises.
The testing should include all sensing devices, keypads, consoles, alarm
indicating devices and any other operational devices that are part of
the system.

 Security and Insurance

Regardless of its capabilities, an alarm system is not a substitute for
property or life insurance. An alarm system also  is not a substitute for
property owners, renters, or other occupants to act prudently to pre-
vent or minimize the harmful effects of an emergency situation.

ii

firealarmresources.com

Summary of Contents for MAXSYS RF4164-433

Page 1: ...d function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read RF4164 433 v4 0 Installation Manual This RF4164 433 V4 0 receiver version is currently supported by all PC4020 DLS 3 downloading files firealarmresources com ...

Page 2: ...tes and uses radio frequency energy and if not installed and used properly in strict accordance with the manufacturer s instructions may cause interference to radio and television reception It has been type tested and found to comply with the limits for Class B device in accordance with the specifications in Subpart B of Part 15 of FCC Rules which are designed to provide reasonable protection agai...

Page 3: ...Wireless Key Reception 9 4 3 Mount the RF4164 433 Receiver and Wireless Devices 9 Deleting Replacing Devices 10 5 1 Replacing Devices 10 5 2 Deleting Devices 10 5 3 Deleting Device Serial Numbers 11 5 4 Deleting a RF4164 433 Module 11 Additional Programming Notes 12 6 1 Device Fail Time 12 6 2 Trouble Conditions 12 Troubleshooting 14 Programming Worksheets 15 INDUSTRYCANADASTATEMENT This class B d...

Page 4: ...perly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or posi tioned Smoke may not be able to reach the smoke detectors such as when the fire is in a chimney walls or roofs or on the other side of closed doors Smoke detectors may not detect smoke from fires on another level of the residence or building Every fire is diff...

Page 5: ...a PC4020 system LCD keypad or using DSC downloading software DLS 3 or higher See the PC4020 Installation Manual Section 3 How to Program 1 2 How to Use This Manual To install and set up the RF4164 433 and wireless devices follow these steps 1 Enroll and temporarily mount the RF4164 433 module see Section 2 2 Enroll and program wireless devices using zones and wireless keys see Section 3 3 Complete...

Page 6: ... Location can be wired up to 750 ft 230 m from the main panel with 22 gauge wire connects to Combus for longer wire runs thicker gauge wire must be used 1 4 Wireless Devices Please refer to the Installation Instruction sheets of the following devices for more information The RF4164 433 v4 0 can receive signals from the following devices WLS912L 433 Glass Break Detector WLS914 433 Pet Immune PIR WS...

Page 7: ... as high and as close to the underside of the first floor as possible The range of the module will be reduced if the unit is mounted below ground level 2 3 Connecting the RF4164 433 The RF4164 433 is connected to the control panel via the Combus CAUTION Remove all power from the panel while connecting modules to the Combus Wire the RF4164 433 to the Combus of the PC4020 according to diagram 1 2 4 ...

Page 8: ...per on Desired Unit 4 Tamper the RF4164 433 i Remove the cover of the RF4164 433 ii Press the case tamper switch located to the right of the terminal strip and release NOTE If equipped the wall tamper will also need to be depressed with the case tamper However it does not need to be released to complete the enrollment 5 The LCD keypad will display RF4164 433 Zn Ex Mod XX Enrolled Record the module...

Page 9: ... system LCD keypad enter 8 Installer s Code 2 EnterRef 001300 togototheEnrollDeviceprogrammingsection This section will only be available if you have already enrolled the RF4164 433 module with the panel see Section 2 5 The LCD keypad will display Enroll Device Serial 3 Lookatthebackofthefirstwirelessdeviceyouwanttoenroll Ifthedevicehasa6 digit serialnumber enteritnow Ifthedeviceonlyhasa5 digitnum...

Page 10: ... key the panel will assign a user number 0101 to 0116 to the key The wireless key enrolled in slot 01 will be given user number 0101 slot 02 will have user number 0102 and so on This allows the panel to transmit and log the arm disarm events performed by each wireless key You can still program access codes for user numbers 0101 to 0116 For example User 0101 arms or disarms using an access code the...

Page 11: ...med function will be executed immediately 5 The LCD keypad will show Select 01 Partition 1 Scroll to the partition you want the button to work in and press to select 6 Repeat steps 3 to 5 until all the buttons are programmed 7 Repeat steps 4 to 6 until all the wireless keys are programmed 8 To exit press NOTE When a wireless key is used to disarm a partition all courtesy pulse outputs enabled for ...

Page 12: ...umber and press to select it The keypad will display Activate Device 6 Activate the device being tested A result will be displayed on the keypad or sounded by the keypad or bell WLS904 433 WLS904P L 433 WLS914 433 N A only Remove the detector from the backplate wait for the result to be presented then reattach the detector to its backplate WS4916 Hold the supplied magnet near the raised line on th...

Page 13: ...will always notify your central station of a nonmedical emergency If these devices do not operate from all points in the installation you will need to move the RF4164 433 receiver Moving the RF4164 433 higher will usually improve the reception If you move the RF4164 433 receiver repeat the tests described in sections 4 1 and 4 2 on all the wireless devices Continue to test the devices until you ha...

Page 14: ...ter If you need to do this you must delete the first device see Deleting Devices below and enroll the second You will also need to change the programming for the new device See Section 3 Enrolling and Programming WLS9XX Wireless Devices 5 To exit press 5 2 Deleting Devices This section describes how to delete any of the enrolled wireless devices from the RF4164 433 receiver and from the system 1 A...

Page 15: ...leting a RF4164 433 Module To delete a RF4164 433 module enter the following at any enrolled keypad 1 Enter Installer s Programming by pressing 8 Installer s Code 2 Enter reference number 0201 to go to Delete Device then press 3 Scroll through the different modules type and select PC41XX Press to select 4 Scroll to the correct module type then to the correct module number For example to delete RF4...

Page 16: ...on with that zone and restore the Zone Supervisory Fault The Device Fail timer will also be reset Change the Supervision Option 1 At an LCD keypad enter 8 Installer s Code 2 Enter Ref 001306 to go to the Supv Window section 3 Devices are listed by zone number in the order in which they were enrolled Scroll to each device Press to turn the supervision option ON or OFF for that device 4 To exit pres...

Page 17: ...vice from its backplate This creates a tamper condition on the zone 2 Refer to the battery installation instructions on the installation sheet of each component Ensure the proper orientation of the batteries as you install them 3 Whenthefreshbatteriesareinplace reattachthecovertothebackplate Thetamper is restored and the zone sends a battery trouble restoral signal to the RF4164 433 receiver The b...

Page 18: ...enrolled Verify that the device is in range of the RF4164 433 receiver Try testing the device in the same room as the receiver Confirm that the RF4164 433 receiver is properly connected to the Combus see section 2 for RF4164 433 receiver setup and wiring instructions Check that you are testing the zone correctly see sections 4 1 and 4 2 for testing instructions Check that the batteries are working...

Page 19: ..._ _ _ _ _ l l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _ l l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _ l Serial Number Zone l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _ l l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l_ _ _ _ _l_ _ _ _ _ l_ _ _ _ _l l_ _ _ _ _l...

Page 20: ..._l l_________l l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l 06 l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l 07 l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l 08 l_____l_____l l_________l l_____l_____l l_________l l_____l_____l l_________l l_____l_____...

Page 21: ...__l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l_____l l________l Zone Supervision No ON OFF l_____l_____l_____l l________l l_____l_____l_____l l________l l_____l_____l____...

Page 22: ...ry devices 15 M Motion detector test 10 Mount devices 11 RF4164 433 11 N Number serial 7 slot 8 Numbers reference 3 P Partition programming forbuttons 9 Placement test 10 Power 5 Problems 16 Programming how to 3 R Reference numbers 3 Remove devices 12 Replace devices 12 S Serial numbers 7 Slot number wireless key 8 Supervision 14 T Testing door window contact 10 motiondetector 10 wireless key 11 T...

Page 23: ...puter software and may include associated media printed materials and online or electronic documentation Any software provided along with the SOFTWARE PRODUCT that is associated with a separate end user license agreement is licensed to You under the terms of that license agreement By installing copying downloading storing accessing or otherwise using the SOFTWARE PRODUCT You agree unconditionally ...

Page 24: ...ODUCT including all component parts themedia andprinted materials any upgrades and thisEULA and provided the recipient agreesto the termsof thisEULA If theSOFTWARE PRODUCT isan upgrade anytransfer must also include allprior versions of theSOFTWARE PRODUCT f Termination Without prejudicetoany other rights DSCmay terminate this EULAif You fail to complywiththe terms and conditionsofthisEULA In suche...

Reviews: