4
G E T T I N G S T A R T E D
NOTE: You cannot have more than 128 zones on the PC4020. If the total number of zones
theoretically available on the zone expanders exceeds the maximum for the panel, you will not
be able to use the extra zones.
A description of how to enroll keypads and modules is in your PC4020
Installation
Manual.
Follow these steps to enroll your RF4164-433 module.
1. At a PC4020 system LCD keypad, enter [
✱
][8][Installer’s Code] to go to the
Installer’s Programming section.
2. Enter Ref #[0200], to go to the
Enroll Module
section.
3
Scroll to
PC41xx Zn. Ex.,
press [
✱
]. The LCD keypad will display
Create Tamper
on Desired Unit.
4. Tamper the RF4164-433:
i) Remove the cover of the RF4164-433
ii) Press the case tamper switch located to the right of the terminal strip and
release
NOTE: If equipped, the wall tamper will also need to be depressed with the case tamper.
However, it does not need to be released to complete the enrollment.
5. The LCD keypad will display
RF4164-433 Zn. Ex. Mod XX Enrolled.
Record the
module number of the RF4164-433 receiver in the
Programming Worksheets.
6. When the module is enrolled, re-secure the connection between the T1 and T2
terminals.
7. To enroll another RF4164-433 module, repeat steps 2 to 6. To exit module
enrollment, press [#].
The RF4164-433 module is now installed and enrolled on the PC4020 system. You can
now enroll and program the wireless devices (see Section 3).