NOTES FOR
INSTALLATIONS
This equipment is UL listed in accordance with UL 1023 (Household Burglar Alarm System Units). This
equipment has not been investigated for compliance with UL 294, Access Control System Units.
This equipment has the capability of being programmed for operational features that are not allowed for UL
recognized installations. To stay within the standard for household applications, the installer should stay within
the following guidelines when configuring the system.
components of the system should be UL listed for the intended application. Note elsewhere in this manual
recommendations for a smoke detector and battery for use with this system.
equipment is listed for “Local” applications only and should not be programmed for “Silent Alarm”
(Section [I zone definitions).
3. Maximum allowed Entry delay = 45 seconds
Maximum allowed Exit delay 60 seconds
Minimum allowed Siren cutoff time 4 minutes
User Bypass must be enabled such that a User Code is required to Bypass zones (Section
light
installer should caution the user to not give system information (for example, Access Codes, Bypass
methods, etc.) to casual users such as babysitters or home service people. Only the “One-Time” use code
should be given to the casual user.
installer should advise the user and note in the user manual:
a) The service organization name and telephone number
b) The programmed Exit time
c) The programmed Entry time
Master Code should be changed from the factory default setting and the new Master Code recorded
in the User manual.
equipment is listed for Local applications only and thus the connection to a Central Receiving Station
via the Digital Communicator has not been evaluated by UL and the following should be noted:
“The Burglar Alarm signal shall not be connected to a police emergency number.”
“The receiving unit to which this equipment transmits signals has not been evaluated by UL.
9. Remote programming shall be disabled.