30

Alarm Cancelled:

 this reporting code will be sent if a valid

access code is entered during the Alarm Cancel window.
If a valid access code is entered during this window, then
the Alarm Cancelled event is logged and sent. When the
central station has acknowledged this reporting code/
event, a keypad ring-back will occur.

[329] - Priority Alarm and Restoral Reporting 
Codes

[F], [A], [P] Alarm: 

 this reporting code will be sent if the

[F] [A] or [P] key is used to generate manual alarms. 

Auxiliary Input Alarm:

 this reporting code will be sent

when PGM2 is being used for 2-wire smoke detectors and
the 2-wire smoke detector goes into alarm. 

[F], [A], [P] Restoral: 

 this reporting code will be sent after

the [F] [A] [P] alarm reporting code is sent.

Auxiliary Input Restoral:

 the panel will transmit this

reporting code when the 2-wire smoke detector has
restored after an alarm.

[330]-[331] - Tamper Reporting Codes, Zones 1-32

If the panel is programmed for Double EOL zones (see
Section 2.10 "Zone Wiring") the panel will report a 

Zone

Tamper Alarm

 reporting code if an open condition is

present on a zone. A different reporting code can be pro-
grammed for each zone for identification. 

[334]-[335] - Tamper Reporting Codes, Zones 1-32

The 

Zone Tamper Restoral

 reporting code will be trans-

mitted immediately when the Tamper condition is
restored.

[338] - Miscellaneous Tamper Reporting Codes

General System Tamper:

General System Tamper:

General System Tamper:

General System Tamper:

 a General System Tamper

General System Tamper

General System Tamper

General System Tamper Report-

ing code will be transmitted when the tamper zone on
any module is violated.

General System Tamper Restoral:

General System Tamper Restoral:

General System Tamper Restoral:

General System Tamper Restoral:

 the General System

General System

General System

General System

Tamper Restoral

Tamper Restoral

Tamper Restoral

Tamper Restoral reporting code will be transmitted when
the tamper zone on the module is restored.
Keypad Lockout:

Keypad Lockout:

Keypad Lockout:

Keypad Lockout: the panel will transmit the Keypad

Keypad

Keypad

Keypad

Lockout

Lockout

Lockout

Lockout reporting code if the lockout is activated.

[339]-[340] - Closing (Arming) Reporting Codes, 
Access Codes 1-32

The panel will transmit a Closing

Closing

Closing

Closing reporting code to indi-

cate the system is armed. A different reporting code can
be transmitted for each User Code, Partition Master Code
and System Master Code to identify who armed the sys-
tem.

[341] - Miscellaneous Closing (Arming) Reporting 
Codes

Closing by Duress Code 33/34:

 a Closing by Duress

Closing by Duress

Closing by Duress

Closing by Duress code

Reporting code will be transmitted in addition to the
Duress reporting code if the system is armed using a
Duress Code.

Closing by Master or Supervisory Code:

 the panel will

transmit a Closing

Closing

Closing

Closing reporting code to indicate the system

is armed. A different reporting code can be transmitted
for each User Code, Supervisory Code and System Master
Code to identify who armed the system.

Partial Closing:

 a Partial Closing

Partial Closing

Partial Closing

Partial Closing reporting code will be

transmitted if the system is armed with zones manually
bypassed. The code will also be transmitted if the system
Auto-arms with zone(s) in violation.

Special Closing: 

a Special Closing

Special Closing

Special Closing

Special Closing reporting code will be

transmitted if tthe system is armed using any of the fol-
lowing methods:

 Quick Arm
 Auto-arm
 Arming via the DLS Software

 Arming via Keyswitch
 Away Function Key Arming
 Arming with the Maintenance Code.
 Stay Function Key arming

Late to Close

Late to Close

Late to Close

Late to Close

:

 A Late to Close

Late to Close

Late to Close

Late to Close reporting code will be

transmitted if the system isn't armed before the auto-arm
start time when the late to close option, (Section 017,
option 5) is enabled.

Exit Fault: 

If an Exit Fault Pre-Alert 

Exit Fault Pre-Alert 

Exit Fault Pre-Alert 

Exit Fault Pre-Alert occurs and Entry

Delay expires before the system is disarmed, Exit Fault
will be logged and this reporting code will be sent.

[342]-[343] - Opening (Disarming) Reporting 
Codes  Access Codes 1-32

The panel will transmit an 

Opening 

reporting code

 to indi-

cate the system is disarmed. A different reporting code
can be transmitted for each user code, the system master
code and system master code to identify who armed the
system.

[344] - Miscellaneous Opening (Disarming) 
Reporting Codes

Opening by Duress Code 33/34: 

Opening by Duress Code 33/34: 

Opening by Duress Code 33/34: 

Opening by Duress Code 33/34: This reporting code will be
transmitted in addition to the duress reporting code if the
system is disarmed using a Duress Code
Opening by Master or Supervisory Code:

Opening by Master or Supervisory Code:

Opening by Master or Supervisory Code:

Opening by Master or Supervisory Code: The panel will
transmit this reporting code to indicate the system is
armed. A different reporting code can be transmitted for
each User Code, Supervisory Code and System Master
Code to identify who armed the system.
Auto Arm Cancellation:

Auto Arm Cancellation:

Auto Arm Cancellation:

Auto Arm Cancellation: This reporting code is transmitted
when the Auto Arming sequence is canceled or Postponed
Special Opening:

Special Opening:

Special Opening:

Special Opening: A Special Opening

Special Opening

Special Opening

Special Opening reporting code will

be transmitted if the system is disarmed using any of the
following methods:

• Disarming using the Maintenance Code
• Disarming via the DLS Software
• Disarming via keyswitch

[345] - Maintenance Alarm Reporting Codes

Battery Trouble Alarm:

 the panel will transmit a Battery

Battery

Battery

Battery

Trouble Alarm

Trouble Alarm

Trouble Alarm

Trouble Alarm reporting code when the backup battery
drops below 11.5 V

DC

.

AC Failure Trouble Alarm:

  the panel will transmit an AC

AC

AC

AC

Failure Trouble Alarm

Failure Trouble Alarm

Failure Trouble Alarm

Failure Trouble Alarm reporting code when the AC to the
panel is lost and the AC Failure Communication Delay
timer expires. 

Bell Circuit Trouble Alarm:

  a Bell Circuit Trouble Alarm

Bell Circuit Trouble Alarm

Bell Circuit Trouble Alarm

Bell Circuit Trouble Alarm

reporting code will be transmitted immediately if an open
condition is measured on the Bell Output of the main
panel.

Fire Trouble Alarm:

  a Fire Trouble Alarm

Fire Trouble Alarm

Fire Trouble Alarm

Fire Trouble Alarm reporting code

will be transmitted immediately when an open condition
is measured on any fire zone. 

Auxiliary Power Supply Trouble Alarm: 

the Auxiliary

Auxiliary

Auxiliary

Auxiliary

Power Supply Trouble Alarm

Power Supply Trouble Alarm

Power Supply Trouble Alarm

Power Supply Trouble Alarm reporting code will be
transmitted if the AUX output is shorted.

TLM Trouble:

  a TLM Trouble

TLM Trouble

TLM Trouble

TLM Trouble reporting code can only be

transmitted if a LINKS1000/2X50 Communicator is being
used (see Section 5.26 LINKS1000 Cellular Communica-
tor). The panel will only transmit the signal after the time
programmed for the TLM Trouble Delay. 

General System Trouble: 

a General System Trouble

General System Trouble

General System Trouble

General System Trouble report-

ing code will be transmitted if the panel detects any of the
following: 

 AC Power Failure
 Low Battery
 AUX Output Trouble

Summary of Contents for PC1555 CP-01

Page 1: ...on on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC1555 CP 01 Version 3 2 DLS2002...

Page 2: ...NOTES...

Page 3: ...ned according to the SIA specification for Contact ID If Automatic Contact ID is enabled see Appendix A for reporting codes that will be used for each zone type Keypad Buzzer When enabled and the syst...

Page 4: ...d Bell Time Out for the system 009 011 5 3 Programmable Outputs Access to PGM Output programming for the main board PC5208 and PC5204 modules Output Attributes in Section in Sections 501 514 Assignmen...

Page 5: ...Decimal Data 9 3 3 Programming Hexadecimal Data 9 3 4 Programming Toggle Options 9 3 5 Viewing Programming 10 Section 4 Keypad Commands 11 4 1 Arming and Disarming 11 4 2 Commands 12 4 3 Function Keys...

Page 6: ...v PC1555 CP 01 Wiring Diagram NOTE Remove CON1 when using PGM2 for 2 wire smoke...

Page 7: ...system master 2 supervisor codes 2 duress 1 maintenance and 1 installer code Expandable to 32 zones Keypads with zone inputs available PC5516Z PC5532Z LCD5500Z LCD5520Z and LCD5501Z Wireless expansio...

Page 8: ...ule requires a 16 5 volt AC 40 VA transformer and 4Ah battery see PC5200 Installation Instructions for details PC5204 Power Supply Output Module The PC5204 can provide up to 1 Amp of additional power...

Page 9: ...ow current output module Dimensions 146mm x 105mm x 25 5mm 5 75 x 4 2 x 1 approximately CMC 1 CMC 1 CMC 1 CMC 1 alternate main control cabinet Commercial Burglary Dimensions 222mm x 298mm x 78mm 11 3...

Page 10: ...he Programming Worksheets should be filled out completely before attempt ing to program the system Step 10 Testing the System Test the panel completely to ensure that all features and functions are op...

Page 11: ...Power Non Power Limited All wiring entry points are designated by the arrows All circuits are classified UL installation power limited except for the battery leads which are not power limited A minimu...

Page 12: ...ys on each keypad may be pro grammed for different operation 1 Enter Installer Programming 2 Press 000 for Keypad Programming 3 Enter 1 to 5 to select function key to program 4 Enter a 2 digit number...

Page 13: ...lly Closed NC Loops To enable normally closed loops programming section 013 option 1 must be ON NOTE This option should only be selected if Normally Closed NC devices contacts are being used Normally...

Page 14: ...or for remotely connecting to the Escort5580 TC module via the LINKS1000 NOTE When using the LINKS1000 Busy Tone Detection must not be used NOTE Keypad zones cannot be used for 24 hr Supervisory or LI...

Page 15: ...y box This is handy if you only need to change the first few program boxes All other locations in the Section will remain unchanged If the key is pressed the panel will turn OFF the Ready light turn O...

Page 16: ...Emergency keys Fire Auxiliary or Panic to advance to the next digit When all the digits in a section have been viewed the panel will exit the section the Ready light will turn OFF and the Armed light...

Page 17: ...at any time by entering 1 see section 1 Zone Bypassing or by using the Away function button If a delay zone is violated during the Exit Delay i e somebody leaves through the designated entry exit doo...

Page 18: ...3 as OFF to ensure that Troubles are displayed correctly The various Troubles are described below Light Trouble 1 Service Required Press 1 to determine the specific Trouble Lights 1 8 will light up t...

Page 19: ...e Escort if installed Attribute 5 Attribute 5 Attribute 5 Attribute 5 For Future Use Attribute 6 Attribute 6 Attribute 6 Attribute 6 For Future Use Attribute 7 Attribute 7 Attribute 7 Attribute 7 Bell...

Page 20: ...exit Keypad Buzzer Control Keypad Buzzer Control Keypad Buzzer Control Keypad Buzzer Control When this option is selected the keypad will allow you to scroll through 21 different keypad sounder tone...

Page 21: ...System Master Code or Partition Master Code must be entered before the panel will allow User Functions to be performed section 4 2 Commands 13 7 1 Command Output Option 1 This function key provides th...

Page 22: ...76 Option 8 Automatic Scrolling of Alarms in Memory The LCD5500Z LCD5520Z keypad allows automatic scrolling through alarms in memory while the keypad is idle This feature if enabled will override the...

Page 23: ...2 205 Assigning Zones to System 555 560 Main Board PC5208 PC5208 Sect 6 Communicator Programming 561 564 PC5204 301 304 Telephone Numbers Para 5 9 International Programming 310 System Account Code 700...

Page 24: ...user then has another 30 second delay before the bell output latches and communications is activated A code is then required to silence the bell output NOTE The Fire Delay will be terminated if a 2nd...

Page 25: ...the Exit Delay or the Away function key is used the Interior Delay Zone will be active at the end of the Exit Delay This zone will cause an instant alarm when violated This zone type will fol low the...

Page 26: ...used to reset power for latching smoke detectors The output will deactivate for five seconds when the 7 2 command is entered see section 7 Command Output Functions The keypad buzzer will not sound fo...

Page 27: ...the PGM1 terminal for operation with the LINKS1000 cellular alarm communicator 17 Away Armed Status This output will activate when the system is armed with the Stay Away zones activated 18 Stay Armed...

Page 28: ...E This option must be OFF if PKP LCD keypads older than version 2 00 are used 4 Tampers Faults Dis play ON Tampers and Faults Do Not Show as Open The panel will not illuminate the respective zone LED...

Page 29: ...red 015 THIRD SYSTEM OPTION CODES Option Definition On Off Description 1 F Key ON F Key Enabled Pressing and holding the F key for 2 seconds will generate a Fire alarm The key pad will sound a set of...

Page 30: ...ng 5 Keypad Backlight ing ON Keypad Backlighting is Enabled All keypads on the system will have backlighting on all of the time OFF Keypad Backlighting is Disabled 6 Power Save Mode ON Power Save Mode...

Page 31: ...ted This feature is to prevent the bell from being activated when arming from inside the premises OFF Bell Squawk on all Arming Disarming Bell Squawks will be heard on all types of arming and dis armi...

Page 32: ...ow zone is open on the sys tem or not This Option is OFF at default 5 Keypad Buzzer Alarm ON Keypad Buzzer Follows Bell Enabled The keypad buzzers will follow the bell activity OFF Keypad Buzzer Follo...

Page 33: ...ately transmit If a second zone alarm occurs in the time period minutes pro grammed in this section the panel will log and trans mit the Police Code event If the second zone alarm occurs after this ti...

Page 34: ...o differentiation between the No Activity Pre alert and the Standard Auto arm Pre alert at a keypad No Activity Arming and Auto arm will log and transmit as a Special Closing 5 5 Partition Zone Progra...

Page 35: ...orting code program it as FF default setting or 00 For a complete description of reporting codes which can be programmed and lists of Automatic Contact ID and SIA format codes see section Appendix A R...

Page 36: ...h the Maintenance Code Stay Function Key arming Late to Close Late to Close Late to Close Late to Close A Late to Close Late to Close Late to Close Late to Close reporting code will be transmitted if...

Page 37: ...er back it will call the central station and transmit the reporting code to indicate a download session is about to begin DLS Lead Out DLS Lead Out DLS Lead Out DLS Lead Out After a downloading sessio...

Page 38: ...tions Section 351 to 376 Pager Format The Communicator Format Communicator Format Communicator Format Communicator Format option for either telephone number can be programmed for Pager format If an ev...

Page 39: ...condition if the telephone line is disconnected If the TLM Enable TLM Enable TLM Enable TLM Enable option is ON the panel will check the telephone line every 10 seconds If the telephone line volt age...

Page 40: ...d before a Telephone Line Trouble is generated is programmed here Valid entries are 000 255 for Trou ble annunciation and transmission LINKS delays of 10 to 2550 Seconds 42 5 Minutes Test Transmission...

Page 41: ...the Third Telephone Number fail a Failure to Communicate Trouble will be generated 7 LINKS Dialing ON Call LINKS as well as Land Line s The control panel will dial the programmed number of attempts th...

Page 42: ...hen transmitting to the central station OFF Contact I D Uses Automatic Reporting Codes The Contact I D communications format will use the automatic reporting codes as shown in Appendix C when transmit...

Page 43: ...f DAT and DATA The LINKS1000 Special Preamble is sent BEFORE the Preamble programmed in Sections 390 to 392 Example Special Preamble Regular Preamble Telephone Number NOTE If this Special Preamble is...

Page 44: ...ng Double Call to contact the panel Valid entries are 001 to 255 seconds 406 Number of Rings to Answer On The value in this section determines how many rings that the panel will automatically pick up...

Page 45: ...e Calculate the average amount of time per day that the panel gains or loses Add or subtract this value seconds from 60 and enter the value Example panel loses an average of 9 seconds per day Instead...

Page 46: ...try to place the call again following the Delay Between Dialing Attempts p OFF Busy Tone Detection Disabled The communicator will use the standard dialing procedure for every attempt 7 Battery Curren...

Page 47: ...To perform a Walk Test do the following 1 Enter Installer Programming 2 Enter Section 901 When any zone is violated the panel will activate the Bell Output for two seconds and log the event to the ev...

Page 48: ...nel Escort5580 TC mod ule PC5132 wireless expander module PC5400 printer module and LINKS2X50 module NOTE Defaulting the main panel does not default the keypads See the Programming Worksheets Appendic...

Page 49: ...to activate an audible Trouble signal within 90 seconds upon loss of microprocessor memory Programming The notes in the programming sections describing the system configura tions for UL Listed instal...

Page 50: ...BV 00 328 Burglary Not Verified This reporting code will be sent after the Burglary Verified Timer expires after a zone alarm occurs A R 3 78 BG 00 328 Alarm Cancelled This reporting code will be sen...

Page 51: ...l station on Phone 1 or 2 after FTC MA R 3 54 YK 00 347 Event Buffer is 75 Full Event buffer is almost full since last upload MA R 6 23 JL 00 347 DLS Lead In Downloading session start MA R 4 11 RB 00...

Page 52: ...r 1 59 Low Temp 1 32 Interior 1 61 Loss of Air Flow 1 33 24 hr Zone Definition SIA Auto Rep Codes Contact ID Auto Rep Codes Zone Alm Rest Zone Alm Rest Delay 1 BA ZZ BH ZZ 1 3A Delay 2 BA ZZ BH ZZ 1 3...

Page 53: ...f devices that may be connected to a line as determined by the total RENs contact the local Telephone Company For products approved after July 23 2001 the REN for this product is part of the product i...

Page 54: ...e complete system should be tested weekly and immediately after a break in an attempted break in a fire a storm an earthquake an accident or any kind of construction activity inside or outside the pre...

Page 55: ...NOTES...

Page 56: ...5108 v2 x No PC5132 v1 X Yes No support for Wireless Keys Pendants or Handheld Keypads PC5132 v2 X Yes PC5132 v3 X Yes PC5200 Yes PC5204 Yes PC5208 Yes PC5320 Yes PC5400 Printer DVACS Mod ule v1 X to...

Reviews: