background image

© 1997 Digital Security Controls Ltd.

1645 Flint Rd., Downsview, Ontario Canada M3J 2J6
Tel: (416) 665 - 8460   Fax: (416) 665-7498

Summary of Contents for PC3OOO

Page 1: ...INSTALLATION MANUAL PC3OOO Version 7 51...

Page 2: ...charge de l ensemble des dispositifs ne d passe pas 100 L indice de charge de cet dispositif est 42 DOC NOTICE NOTICE The Canadian Department of Communications label identifies certified equipment Thi...

Page 3: ...er s Test ____________________ Q 6 Master Code 0 _____________ 10 Setting the Clock __________________ Q 6 Master Code 1 _____________ 10 Auto arm Time of Day _____________ Q 6 Master Code 2 _________...

Page 4: ...umber 1 _____________________________ 19 26 Downloading Access Code ____________________________________________ 19 27 Communicator Format Options _________________________________________ 19 28 Progr...

Page 5: ...ttery Transformer required 16 5 VAC 40VA Dimensions 11 x 11 8 x 3 3 deep 279 x 300 x 84 mm Weight 6 5 lbs 3 kg Remote Keypad Specifications PC3000RK Four wire QUAD hook up and up to 3 keypads per syst...

Page 6: ...tors a number of possible trouble conditions including An active battery supervision circuit that periodically tests the battery under load A loss of the AC power supply A supervised circuit trouble c...

Page 7: ...ed to the bell terminals may go on for a few seconds The Armed light may be on or off the first time the panel is powered The last armed disarmed condition is stored in the EEPROM memory so the panel...

Page 8: ...ble See the Programming Guide section 28 for a list of options for the PGM OUT output The PGM OUT is a 50 mA maximum switch to ground A 100 ohm current limiting resistor is connected in series A small...

Page 9: ...for testing and programming PC3000 systems Connect the transformer wait approx 5 seconds Enter a few keypad commands and open a zone to be sure that the panel and keypad are responding to signals If...

Page 10: ...sleeping area and the rest of the family unit FIG 2 In the family living units with more than one sleeping area a smoke detector should be located to protect each sleeping area FIG 3 A smoke detector...

Page 11: ...eypad buzzer will beep quickly Exit the premises through the designated exit entry door At the end of the allowed exit time all lights on the keypad will go out except the Armed light See the Installe...

Page 12: ...grammed for 1 to 99 minutes See Programming Guide section 22 3 Day Zone Trouble This trouble applies only to zones which have been programmed as day zones Programming Guide section 16 17 A day zone cr...

Page 13: ...5 command If the Master Code is forgotten and the panel is left armed the entire programming can be reset to factory default by using the Hardware Reset method described on page 22 7 To successfully p...

Page 14: ...on then a valid 4 digit access code is required to abort the auto arm sequence The auto arm will be attempted at the same time the following day Auto arm abort with transmission Any time an auto arm i...

Page 15: ...Use Code must be used for arming before it is erased Quick Exit Q 0 When Armed Entering Q 0 when the system is fully armed will allow the user 2 minutes to exit the premises through any delay zone wit...

Page 16: ...he panel and program it as described below Enter the Installer s Programming section and edit the following sections Q 8 Installer s Code Section Printer Only Monitored and Printer 01 Do not program P...

Page 17: ...zone light 7 is off and an answering machine is connected and it is set to answer before the panel the panel will be unable to receive a call from a downloading computer If the panel is set to answer...

Page 18: ...Installers code portion of the command Just enter the number of another programming section When programming a section it is possible to exit by pressing Only the data entered before pressing will be...

Page 19: ...anging the reporting codes in a section only code entries up to the one which is being changed need to be entered Press to exit from the programming sequence Only codes up to the last one entered will...

Page 20: ...ower Supply Trouble 11 Reporting Codes for Closing Arming with Access Codes 1 to 8 The reporting codes in sections 11 to 14 are used to identify Openings and Closings disarming and arming of the syste...

Page 21: ...expires no alarm will be generated Type 7 and 8 Delay zones are used where a longer entry delay time is required such as with a garage door With these two zone types the exit delay is the same as the...

Page 22: ...trouble only armed or disarmed TLM Telephone Line Monitoring 6 Light off Accepts 2300 Hz standard handshake Light on Accepts 1400 Hz handshake for Radionics formats 3 4 B and C in section 27 See Radio...

Page 23: ...Vertex 20 BPS 2300 Hz handshake 3 1 and 4 1 4 2 non extended format 2 Silent Knight fast 20 BPS 1400 Hz handshake 3 1 and 4 1 4 2 non extended format 3 Radionics 2300 1400 Hz handshake 3 1 4 2 non ex...

Page 24: ...lity output Q 7 Group A access code 5 Utility output Q 7 Group B access code These options change the PGM OUT terminal to different options used with the keypad utility output Q 7 command See Utility...

Page 25: ...programmed with a 2 in Section 33 to call the 2nd phone number only It is necessary to program both the 1st and 2nd phone number locations with the same telephone number Notes 1 The following restrict...

Page 26: ...Call back disabled Light on Call back enabled See Downloading 48 Panel Identification Code Program using the same method as sections 24 25 and 26 49 Printer Configuration 1 Light off Not 110 baud Lig...

Page 27: ...nds where 00 means no delay If the system is disarmed before the delay in transmission expires no transmission will take place 53 Auto arm Abort Reporting Code This code is programmed the same as sect...

Page 28: ...digit Zone 2 Alarm Zone 6 Alarm Enter Q1Q HEX A to transmit a 0 Zone 3 Alarm Zone 7 Alarm A 0 digit is 10 pulses Zone 4 Alarm Zone 8 Alarm 06 Alarm Reporting Codes Zones 9 to 16 Page 15 Zone 9 Alarm Z...

Page 29: ...ission reports with sections 11 to 14 AC Failure Trouble openings closings Day Zone s Trouble Bell Circuit Trouble Fire Zone Trouble Auxiliary Power Supply Trouble 11 Reporting Codes for Closing Armin...

Page 30: ...pad Auxiliary Alarm A openings closings Keypad Panic Restoral P Keypad Fire Restoral F Keypad Auxiliary Restoral A Periodic Test Transmission 16 Zone Definitions for Zones 1 to 8 Page 17 Note When def...

Page 31: ...eout Restorals on disarming Off Zone Light 3 Alarm display while armed No alarm display armed Off Zone Light 4 DTMF dialing Pulse dialing Off Zone Light 5 N C zones EOL resistors zones Off Zone Light...

Page 32: ...Time in minutes 3 0 AC Failure Transmission Delay in minutes 5 0 Normal Zone Response Time x 10 ms 3 0 Test Transmission Cycle Time in days 23 System Clock Times Page 19 Default 9 9 9 9 Automatic Armi...

Page 33: ...hake 3 1 extended format A Silent Knight fast 20 BPS 1400 Hz handshake 3 1 extended format B Radionics 2300 1400 Hz handshake 3 1 extended format C Radionics 2300 1400 Hz handshake 3 1 extended with p...

Page 34: ...Light 2 On Zone Light 3 On Zone Light 4 On Zone Light 5 On Zone Light 6 On Zone Light 7 On Zone Light 8 30 Zone Group B Assignment Page 21 Default On Zone Light 1 On Zone Light 2 On Zone Light 3 On Z...

Page 35: ...Group A Openings and Closings 1 Access Codes Group B Openings and Closings 1 Priority Alarms and Restorals 1 Maintenance Alarms and Restorals Enter 0 No transmissions for this group 1 Call 1st phone n...

Page 36: ...On Zone Light 2 On Zone Light 3 On Zone Light 4 On Zone Light 5 On Zone Light 6 On Zone Light 7 On Zone Light 8 44 Access Bypass Mask Codes 9 to 16 Page 22 Default On Zone Light 1 On Zone Light 2 On...

Page 37: ...15 all lights on On Zone Light 4 At least one light must be on Off Zone Light 5 Downloading answer enabled Downloading answer disabled Off Zone Light 6 User initiated call up No user initiated call up...

Page 38: ...Zone Light 7 Answering machine over ride Answering machine over ride timer 120 seconds timer 60 seconds Off Zone Light 8 Bell shutdown active Bell shutdown not active 52 Delay Before Transmission Pag...

Page 39: ...__________ ______________________________________________________________________ 6 ____________________________ ______________________________________________________________________ 7 ______________...

Page 40: ...HOOKUP DIAGRAMS 36...

Page 41: ...22AWG 540 164m 20AWG 850 259m 19AWG 1000 305m 18AWG 1360 414m FIRE CIRCUIT HOOKUP Smoke Detector Power Loop Wiring Chart Loop Current mA AWG14 AWG16 AWG18 AWG19 AWG22 Maximum wire run to EOL relay in...

Page 42: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Digital Security Controls Ltd This warranty contains the...

Page 43: ...1997 Digital Security Controls Ltd 1645 Flint Rd Downsview Ontario Canada M3J 2J6 Tel 416 665 8460 Fax 416 665 7498...

Page 44: ...29000543 R7...

Reviews: