8
Normally Closed Loops . . . . . . . . . . . . Section [013], Option [1]
Single End Of Line (EOL) Resistors
To enable panel detection of single end-of-line resistors, pro-
gramming section [013], options [1] and [2] must be OFF.
NOTE:
This option should be selected if either Normally Closed
(NC) or Normally Open (NO) detection devices or contacts are
being used
.
End of Line Resistors . . . . . . . . . . . . . . Section [013], Option [1]
Single End of Line Resistors . . . . . . . . . Section [013], Option [2]
Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if the
zone is in alarm, tampered or faulted.
To enable panel detection of double end of line resistors, pro-
gramming section [013], option [1] must be OFF and option [2]
must be ON.
NOTE:
If the Double EOL supervision option is enabled, all hard-
wired zones must be wired for Double EOL resistors, except for
Fire and 24 Hour Supervisory zones.
Do not wire DEOL resistors on keypad zones.
Do not use DEOL resistors for Fire zones or 24 Hour Supervisory
zones. Do not wire Fire zones to keypad zone terminals if the
DEOL supervision option is selected.
This option can only be selected if Normally Closed (NC) detection
devices or contacts are being used. Only one NC contact can be
connected to each zone.
The following chart shows zone status under certain conditions:
End-of-Line Resistors . . . . . . . . . . . . . Section [013], Option [1]
Double End-of-Line Resistors . . . . . . . Section [013], Option [2]
Fire Zone Wiring - 4-wire Smoke Detectors
All zones defined as Fire
see section 5.3 Basic Programming on
)
must be wired according to the following diagram:
For a complete description of how fire zones operate, see section
5.3 Basic Programming on page 20
Fire Zone Wiring - 2-wire Smoke Detectors
If PGM 2 has been programmed for 2-Wire Smoke Detector
con-
nection
see section 5.3 Basic Programming on page 20
, the
detectors must be wired according to the following diagram:
For a complete description of how fire zones operate, see section
5.3 Basic Programming on page 20
Keyswitch Zone Wiring
Zones may be programmed to be used as keyswitch arming
zones and must be wired according to the following diagram:
For a complete description of how keyswitch zones operate, see
section 5.3 Basic Programming on page 20
LINKS1000 Supervisory (24 Hour Supervisory)
When using the LINKS1000 cellular communicator, any main
board zone may be configured for LINKS1000 Supervision. Pro-
gram this zone as zone type (09), 24 Hour Supervisory in section
[001].
With a 24 Hour Supervisory zone, if the LINKS1000 experiences
a trouble, the zone will be violated, causing the panel to report
the event to the central station. This type of zone
always
requires
a single EOL resistor (5600
Ω
).Refer to Links 1000 Installation
Manual wiring diagram for installation.
Loop Resistance
Loop Status
0
Ω
(shorted wire, loop shorted)
Fault
5600
Ω
(contact closed)
Secure
Infinite (broken wire, loop open)
Tamper
ANY Z
TERMINAL
ANY COM
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
11200
Ω
(contact open)
Violated