P r o g r a m m i n g S e c t i o n s :
5 . 4 A d v a n c e d P r o g r a m m i n g
33
[020] - Keypad Zone Assignment
Assigning Keypad Zones
Each keypad has a zone input to which a device (i.e. a door con-
tact) can be connected. (See section 2.10
page 9 for wiring information.)
Once the keypad zones are installed. Enter the 2-digit zone des-
ignated for each keypad (slot) from 01-64.
NOTE:
24 Hour Supervisory (LINKS) and LINKS Answer Zones can-
not be used on Keypad Zones.
Fire zones can not be used on keypad zones if DEOL is enabled.
Hookup -If NC is enabled, a short across the keypad zone is
required (from Z to B/Ground). -If EOL or DEOL is enabled, a
5.6K
Ω
across the keypad zone is required (from Z to B/Ground).
[030] - Fast Loop Response
An eight bit toggle option controls which main board zones have
Fast Loop (36 ms) or Normal Loop Response (540 ms). Fast loop
response is typically used for vibration sensors.
5.4 Advanced Programming
[101]-[164] Zone Attributes
T
he two sets of attributes (1-8 and 9-16) may be toggled by
pressing ‘9’ within any zone’s attribute section. If the Ready
LED is on, the keypad is indicating Zone Attributes 1-8; if the
Ready and Armed LED’s are on, the keypad is indicating Zone
Attributes 9-16. T
he following options can be enabled or dis-
abled by zone.
[101]-[164] ZONE ATTRIBUTES
Option
Attribute
On/Off
Description
1
Bell
ON
An alarm will cause the bell output to activate.
OFF
Silent Alarm
2
Bell Type
ON
The bell output will be steady when the zone is in alarm.
OFF
The bell output will pulse when the zone is in alarm.
3
Chime
ON
Every keypad will chime when the zone is violated and when the zone is secured. Door
Chime will work in both the armed and disarmed states.
OFF
The zone will not chime the keypads.
4
Bypass
ON
The zone may be manually bypassed.
OFF
The zone cannot be bypassed.
5
Force Arming
ON
The system (partition) may be armed with the zone violated. The zone will be temporarily
bypassed, and when the zone is secured it will be added back into the system.
OFF
The system cannot be armed if this zone is open.
6
Swinger Shutdown
ON
The zone will shut down after a programmed number of alarms, inhibiting further trans-
missions to the monitoring station. The bell will follow Swinger Shutdown.
OFF
Swinger Shutdown disabled
7
Transmission Delay
ON
The reporting of zone alarms will be delayed for the programmed time. If a valid access
code is entered within this time, no alarm signal will be communicated.
OFF
When an alarm occurs, the reporting code is transmitted immediately.
8
Wireless ON
Zone is Wireless. The zone will ignore the main board zone (if applicable) and respond to
the corresponding zone enrolled on the PC5132.
OFF
Zone is Hardwired. The zones uses the corresponding hardwired zone.
9
Cross Zone
ON
Zone is a Cross Zone. Zone is enabled for Cross Zoning.
OFF
Zone is not a Cross Zone. Zone is not enabled for Cross Zoning. The Default state for the
Cross Zone Attribute is OFF for all zone types.
NOTE:
DO NOT change Fire Zones attributes from the default settings.