background image

WARNING 

Please Read Carefully

N o t e   t o   I n s t a l l e r s

This warning contains vital information. As the only individual in contact with system users, it is your
responsibility to bring each item in this warning to the attention of the users of this system.

S y s t e m   Fa i l u r e s

This system has been carefully designed to be as effective as possible. There are circumstances, however,
involving fire, burglary, or other types of emergencies where it may not provide protection. Any alarm sys-
tem of any type may be compromised deliberately or may fail to operate as expected for a variety of reasons.
Some but not all of these reasons may be:

 

Inadequate Installation

A security system must be installed properly in order to provide adequate protection. Every installation
should be evaluated by a security professional to ensure that all access points and areas are covered. Locks
and latches on windows and doors must be secure and operate as intended. Windows, doors, walls, ceilings
and other building materials must be of sufficient strength and construction to provide the level of protection
expected. A reevaluation must be done during and after any construction activity. An evaluation by the fire
and/or police department is highly recommended if this service is available.

 Criminal Knowledge

This system contains security features which were known to be effective at the time of manufacture. It is
possible for persons with criminal intent to develop techniques which reduce the effectiveness of these fea-
tures. It is important that a security system be reviewed periodically to ensure that its features remain effec-
tive and that it be updated or replaced if it is found that it does not provide the protection expected.

 Access by Intruders

Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection by
moving through an area of insufficient coverage, disconnect a warning device, or interfere with or prevent
the proper operation of the system.

 Power Failure

Control units, intrusion detectors, smoke detectors and many other security devices require an adequate
power supply for proper operation. If a device operates from batteries, it is possible for the batteries to fail.
Even if the batteries have not failed, they must be charged, in good condition and installed correctly. If a
device operates only by AC power, any interruption, however brief, will render that device inoperative while
it does not have power. Power interruptions of any length are often accompanied by voltage fluctuations
which may damage electronic equipment such as a security system. After a power interruption has occurred,
immediately conduct a complete system test to ensure that the system operates as intended.

 Failure of Replaceable Batteries

This system’s wireless transmitters have been designed to provide several years of battery life under normal
conditions. The expected battery life is a function of the device environment, usage and type. Ambient con-
ditions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the
expected battery life. While each transmitting device has a low battery monitor which identifies when the
batteries need to be replaced, this monitor may fail to operate as expected. Regular testing and maintenance
will keep the system in good operating condition.

 Compromise of Radio Frequency (Wireless) Devices

Signals may not reach the receiver under all circumstances which could include metal objects placed on or
near the radio path or deliberate jamming or other inadvertent radio signal interference.

 System Users

A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary
physical disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is
important that all system users be trained in the correct operation of the alarm system and that they know
how to respond when the system indicates an alarm.

 Smoke Detectors

Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of rea-
sons, some of which follow. The smoke detectors may have been improperly installed or positioned. Smoke
may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roofs, or on the
other side of closed doors. Smoke detectors may not detect smoke from fires on another level of the resi-
dence or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot
sense all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by
carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances when there is insufficient warn-
ing to allow all occupants to escape in time to avoid injury or death.

 Motion Detectors

Motion detectors can only detect motion within the designated areas as shown in their respective installation
instructions. They cannot discriminate between intruders and intended occupants. Motion detectors do not
provide volumetric area protection. They have multiple beams of detection and motion can only be detected
in unobstructed areas covered by these beams. They cannot detect motion which occurs behind walls, ceil-
ings, floor, closed doors, glass partitions, glass doors or windows. Any type of tampering whether intentional
or unintentional such as masking, painting, or spraying of any material on the lenses, mirrors, windows or
any other part of the detection system will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in temperature. However their effectiveness
can be reduced when the ambient temperature rises near or above body temperature or if there are intentional
or unintentional sources of heat in or near the detection area. Some of these heat sources could be heaters,
radiators, stoves, barbeques, fireplaces, sunlight, steam vents, lighting and so on.

 Warning Devices 

Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if
there is an intervening wall or door. If warning devices are located on a different level of the residence or
premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices may
be interfered with by other noise sources such as stereos, radios, televisions, air conditioners or other appli-
ances, or passing traffic. Audible warning devices, however loud, may not be heard by a hearing-impaired
person.

 Telephone Lines

If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time.
Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may
be difficult to detect.

 Insufficient Time

There may be circumstances when the system will operate as intended, yet the occupants will not be pro-
tected from the emergency due to their inability to respond to the warnings in a timely manner. If the system
is monitored, the response may not occur in time to protect the occupants or their belongings.

 Component Failure

Although every effort has been made to make this system as reliable as possible, the system may fail to func-
tion as intended due to the failure of a component.

 Inadequate Testing

Most problems that would prevent an alarm system from operating as intended can be found by regular test-
ing and maintenance. The complete system should be tested weekly and immediately after a break-in, an
attempted break-in, a fire, a storm, an earthquake, an accident, or any kind of construction activity inside or
outside the premises. The testing should include all sensing devices, keypads, consoles, alarm indicating
devices and any other operational devices that are part of the system.

 Security and Insurance

Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm sys-
tem also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or
minimize the harmful effects of an emergency situation.

Limited Warranty

Digital Security Controls Ltd. warrants the original purchaser that for a period of twelve months from the
date of purchase, the product shall be free of defects in materials and workmanship under normal use. Dur-
ing the warranty period, Digital Security Controls Ltd. shall, at its option, repair or replace any defective
product upon return of the product to its factory, at no charge for labour and materials. Any replacement and/
or repaired parts are warranted for the remainder of the original warranty or ninety (90) days, whichever is
longer. The original owner must promptly notify Digital Security Controls Ltd. in writing that there is defect
in material or workmanship, such written notice to be received in all events prior to expiration of the war-
ranty period.

I n t e r n a t i o n a l   Wa r r a n t y

The warranty for international customers is the same as for any customer within Canada and the United
States, with the exception that Digital Security Controls Ltd. shall not be responsible for any customs fees,
taxes, or VAT that may be due.

Wa r r a n t y   P r o c e d ur e

To obtain service under this warranty, please return the item(s) in question to the point of purchase. All
authorized distributors and dealers have a warranty program. Anyone returning goods to Digital Security
Controls Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any
shipment whatsoever for which prior authorization has not been obtained.

C o n d i t i o n s   t o   Vo i d   Wa r r a n t y

This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover:

damage incurred in shipping or handling;

damage caused by disaster such as fire, flood, wind, earthquake or lightning;

damage due to causes beyond the control of Digital Security Controls Ltd. such as excessive voltage,
mechanical shock or water damage;

damage caused by unauthorized attachment, alterations, modifications or foreign objects;

damage caused by peripherals (unless such peripherals were supplied by Digital Security Controls Ltd.);

defects caused by failure to provide a suitable installation environment for the products;

damage caused by use of the products for purposes other than those for which it was designed;

damage from improper maintenance;

damage arising out of any other abuse, mishandling or improper application of the products.

Digital Security Controls Ltd.’s liability for failure to repair the product under this warranty after a reason-
able number of attempts will be limited to a replacement of the product, as the exclusive remedy for breach
of warranty. Under no circumstances shall Digital Security Controls Ltd. be liable for any special, incidental,
or consequential damages based upon breach of warranty, breach of contract, negligence, strict liability, or
any other legal theory. Such damages include, but are not limited to, loss of profits, loss of the product or any
associated equipment, cost of capital, cost of substitute or replacement equipment, facilities or services,
down time, purchaser’s time, the claims of third parties, including customers, and injury to property.

D i s c l a i m e r   o f   Wa r r a n t i e s

This warranty contains the entire warranty and shall be in lieu of any and all other warranties,
whether expressed or implied (including all implied warranties of merchantability or fitness for a par-
ticular purpose) And of all other obligations or liabilities on the part of Digital Security Controls Ltd.
Digital Security Controls Ltd. neither assumes nor authorizes any other person purporting to act on
its behalf to modify or to change this warranty, nor to assume for it any other warranty or liability
concerning this product.

This disclaimer of warranties and limited warranty are governed by the laws of the province of
Ontario, Canada.

WARNING: Digital Security Controls Ltd. recommends that the entire system be completely tested on a
regular basis. However, despite frequent testing, and due to, but not limited to, criminal tampering or electri-
cal disruption, it is possible for this product to fail to perform as expected.

I n s t a l l e r ’s   L o c k o u t

Any products returned to DSC which have the Installer’s Lockout option enabled and exhibit no other prob-
lems will be subject to a service charge.

O u t   o f   Wa r r a n t y   R e p a i r s

Digital Security Controls Ltd. will at its option repair or replace out-of-warranty products which are returned
to its factory according to the following conditions. Anyone returning goods to Digital Security Controls
Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment
whatsoever for which prior authorization has not been obtained.

Products which Digital Security Controls Ltd. determines to be repairable will be repaired and returned. A
set fee which Digital Security Controls Ltd. has predetermined and which may be revised from time to time,
will be charged for each unit repaired.

Products which Digital Security Controls Ltd. determines not to be repairable will be replaced by the nearest
equivalent product available at that time. The current market price of the replacement product will be
charged for each replacement unit.

Summary of Contents for PC5020

Page 1: ...This manual contains information on limitations regarding product use and function and informa tion on the limitations as to liability of the manufacturer The entire manual should be carefully read PC...

Page 2: ......

Page 3: ...c Contact ID is enabled reporting codes will be automatically assigned for each zone type programmed Keypad Buzzer Alarm When enabled and the system or Partition is in alarm all assigned keypad buzzer...

Page 4: ......

Page 5: ...How to Enter Installer Programming 10 3 2 Programming Decimal Data 10 3 3 Programming Hexadecimal Data 10 3 4 Programming Toggle Options 10 3 5 Viewing Programming 11 Section 4 Keypad Commands 12 4 1...

Page 6: ...ii PC5020 Wiring Diagram...

Page 7: ...sed Single EOL or Double EOL zone supervision 34 zone types 8 Programmable zone options Up to 8 partitions Audible Alarm Output 700mA supervised bell output current limit 3 amps 12 VDC Steady or pulse...

Page 8: ...number of zones on the system Up to 7 modules can be connected to increase the system zones to a maximum of 64 See the PC5108 Installation Instructions Sheet NOTE PC5108 v1 0 and lower modules can on...

Page 9: ...E Do not use the PC5700 and PC5720 v1 x and lower mod ules with PC5108 v2 0 and higher modules on the same system Cabinets Several different cabinets are available for the PC5020 modules They are as f...

Page 10: ...d from the system To confirm that each module is properly supervised follow the guidelines provided in section 2 7 Step 10 Programming the System Sections 4 5 Section 4 0 provides a complete descripti...

Page 11: ...s Operation and Wiring The Keybus is used by the panel to communicate with all mod ules connected and by the modules to talk to the panel The RED and BLK terminals are used to provide power while YEL...

Page 12: ...on Instruction Sheet for the correct jumper settings he following is a diagram of the PC5108 zone expander module showing the location of the jumper switches Refer to the mod ule s Installation Instru...

Page 13: ...eypad In LED keypads zone lights will be turned on according to what modules the panel has found on the system Refer to the following chart Keypad Light Module Device Present 1 Keypad 1 2 Keypad 2 3 K...

Page 14: ...Fire Zone Wiring 4 wire Smoke Detectors All zones defined as Fire see section 5 3 Basic Programming on page 20 must be wired according to the following diagram For a complete description of how fire...

Page 15: ...screw at the bottom of the unit Locate the five terminals on the keypad circuit board Connect the four Keybus wires from the control panel the red wire to R the black to B the yellow to Y and the gre...

Page 16: ...am boxes All other locations in the Section will remain unchanged If the key is pressed the panel will turn OFF the Ready light turn ON the Armed light and exit you from the Section 3 3 Programming He...

Page 17: ...mergency Keys Fire Auxiliary or Panic to advance to the next digit When all the digits in a section have been viewed the panel will exit the section the Ready Light will turn OFF and the Armed light w...

Page 18: ...etermine what abilities the code will have By default each code has the attributes of the code used to pro gram it For example if you use the Master code to program other access codes the new codes wi...

Page 19: ...is is a convenience for users that want to arm the panel while at home Using this method users do not have to bypass the interior zones manually Users can add the Stay Away zones back into the system...

Page 20: ...esponding to the present trouble conditions will be ON When using an LCD keypad the trouble conditions will be listed on the display Users can scroll through the list of present trouble conditions usi...

Page 21: ...on the keypad sound the keypad buzzer for two seconds test the main panel PC5200 PC5204 battery send a System Test Reporting code if programmed 5 Enable DLS Downloading When 5 is pressed the panel wi...

Page 22: ...e is tripped or if the zone is not restored after two minutes the panel will start entry delay NOTE If Quick Exit is used on a partitioned system Keypad Blanking and Access Code Required to Remove Bla...

Page 23: ...lp session with the Escort For more information Refer to the PC5936 Installation Manual NOTE While the voice prompt help is active users will not be able to disarm the system using Wireless Keys 16 0...

Page 24: ...he key pad will then display the status of the selected partition and allow normal operation A Partition keypad will display the status of the Partition it is assigned to A user with access to more th...

Page 25: ...rd PC5208 51 202 265 Assigning Zones to Partitions 35 555 560 PC5208 51 Communicator Programming 35 561 564 PC5204 51 301 304 Telephone Numbers 36 International Programming 52 310 System Account Code...

Page 26: ...he bells will silence and the transmission will be aborted If the alarm has been acknowledged and the smoke detec tor has not been restored to normal the bell output will activate after 90 seconds the...

Page 27: ...Zone Follower automation applications NOTE This zone type will be active in Walk Test Tampers and Faults Zones programmed as 24 Hour Non alarm type will not cause alarms Alarms on this zone will not...

Page 28: ...e Section 990 Installer Lockout Disable Section 991 007 Master Code 008 Maintenance Code This is a Arm Disarm only code It can not be used to bypass activate 7 outputs program other user codes or ente...

Page 29: ...he entry and exit times It can be used to turn on a courtesy light near the exit door for the duration of the entry exit times Upon activation during an entry delay the output will remain active for 2...

Page 30: ...t any keypad When any output is acti vated three acknowledgment beeps are sounded Refer to Section 501 and 551 for more information on Attributes NOTE If there are multiple outputs programmed with the...

Page 31: ...er of invalid master duress user or installer access code entries to reach keypad lockout When keypad lockout occurs the system is rendered inoperative via keypad for the programmed duration When any...

Page 32: ...nate the Trouble LED when any troubles are present on the System in both the armed and disarmed state OFF Panel Shows Only Fire Troubles While Armed The panel will illuminate the Trouble LED for all t...

Page 33: ...2 Zone defini tions When the panel is armed it will use the Entry Delay for the first Delay zone violated NOTE This feature must not be used with two or more partitions NOTE If the panel is armed usin...

Page 34: ...l activity on another Delay zone will ini tiate its respective alarm sequence If the Delay zone is still open two minutes after the 0 command is entered the Entry Delay will be initiated If armed in t...

Page 35: ...zer condition except Door Chime The keypad lights will return to the off state after 30 seconds of keypad inactivity OFF Power Save Mode Disabled 016 Option 7 Bypass Status Display ON Bypass Status Di...

Page 36: ...Auto arm Pre alert will still occur if there is a time programmed for that day if this option is enabled This option does not directly affect the functionality of auto arm If Late to Close is enabled...

Page 37: ...ogrammed for the above Zone the system will verbally annunciate after the beeps South Bedroom Window See associated Installation Manuals NOTE Only beeps are annunciated on a zone restore OFF Verbal Do...

Page 38: ...arm sequence This option is dependent on the programming of the Burglary Verification Options Sec tion 018 Option 6 It is not enabled if Police Code is enabled This option will not function on zones t...

Page 39: ...Alarm 2 Bell Type ON The bell output will be steady when the zone is in alarm OFF The bell output will pulse when the zone is in alarm 3 Chime ON Every keypad will chime when the zone is violated and...

Page 40: ...ow Delay Timer This option affects the Delayed 24Hr Waterflow zone type The value programmed in this section is the time for which the zone has to be violated before going into alarm Valid entries are...

Page 41: ...telephone number after failing to communicate on the 1st tele phone number NOTE For Alternate Dial to work properly the 3rd telephone Number must be both enabled and programmed Telephone numbers can...

Page 42: ...317 Partition 1 8 Account Codes These Account Codes are used by the panel when communicat ing events for Partitions 1 8 when using formats other than SIA NOTE All Partition Account Codes are 4 digits...

Page 43: ...ntries for the Burglary Verified timer are 000 255 minutes 000 to disable 8 Alarm Canceled If an alarm event is sent after transmission delay has expired then a cancel window time will start If a vali...

Page 44: ...l be transmitted as soon as the problem is corrected These codes are sent to the System Maintenance Call Direction Group 4 Fire Trouble Restore An open circuit on any Fire Zone will cause this trouble...

Page 45: ...y be delayed see Section 377 A low battery restore may only take place after the alarm sensing device has been tampered and the batteries have been changed These reporting codes are transmitted to the...

Page 46: ...Bypassed zones will not be identified when partial closing the system NOTE Do not program the second telephone number for the SIA reporting code format Section 360 if the Automatic Reporting Code opt...

Page 47: ...an reporting an alarm zone 1 the Contact ID format can also report the type of alarm such as Entry Exit alarm zone 1 If Contact ID Sends Automatic Reporting Codes is selected the panel will automatica...

Page 48: ...ate the bell output in the case of a TLM trouble while the system is armed the TLM Audible Bell When Armed option must be selected When the trouble condition is restored the panel can send a TLM Resto...

Page 49: ...timer NOTE If global zones are used with communications delay then to stop all alarms from being sent when the communications delay expires access codes must be entered on all partitions that went in...

Page 50: ...med When a zone is violated and restored while the system is disarmed Stay armed Interior Interior Delay Interior Stay Away or Delay Stay Away zones only The activity delinquency timer will be ignored...

Page 51: ...Number Disabled The 3rd Phone number will not be used 6 3rd Phone Number ON Alternate Dialing Enabled 1st 3rd After each dialing attempt the communicator switches between the 1st Phone Number and 3rd...

Page 52: ...confirm to the end user that the Closing Code was sent and received OFF Closing Confirmation Disabled There will be no keypad ringback when a Closing reporting code is successfully transmitted to a p...

Page 53: ...ram this select both the telephone number and the LINKS1000 options for the Communicator Call Direction Options for the event In addition the Call LINKS1000 as well as Land Line option must be selecte...

Page 54: ...on is enabled or the Number of Rings is programmed to be more than 0 If the User Initiated Call Up option is enabled the user can have the panel initiate a call to the downloading computer by pressing...

Page 55: ...grammed as 19 Command Output 1 the settings for output attributes 1 2 and 5 must be the same This does not apply to outputs pro grammed as types 09 and 10 NOTE Attribute 3 must be ON for PGM output op...

Page 56: ...he corresponding 7 command is entered PGM Output Types 19 22 5 Access Code Options ON Access Code Required for Activation OFF No Access Code Required for Activation Attribute 3 is available for all Ou...

Page 57: ...heck as well as a Battery Check on all peripheral modules supported by a backup battery OFF Arming not Inhibited The system can be armed regardless of the presence of an AC or DC trouble and will not...

Page 58: ...e Local Mode option is OFF the panel will send communicated events to the PC5108L Module Downlook will initiate when requested See your PC5108L Installation Manual for more information See Periodic Ca...

Page 59: ...on is entered the module will be deleted from the system Once executed all pending Supervisory Trouble Restores will not be logged or transmitted 903 Module Supervision Field When this mode is entered...

Page 60: ...wer up the control NOTE AC power must be used to power the panel The panel will not default if the battery is used Factory Default Main Panel Software and other Modules 1 Enter Installer Programming 2...

Page 61: ...pansion modules or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm Two zones on the same partition go into alarm during any given armed to armed period incl 24Hr zones A...

Page 62: ...f time days or hours for delin quency has expired without zone activity or without system being armed MA R 4 54 CD 00 347 Wireless Device Low Battery Trouble Rest Wireless zones panic pendants handhel...

Page 63: ...UH ZZ 1 3A 24Hr Burg BA ZZ BH ZZ 1 3A 24Hr Holdup HA ZZ HH ZZ 1 22 24Hr Gas GA ZZ GH ZZ 1 5A 24Hr Heat KA ZZ KH ZZ 1 5A 24Hr Medical MA ZZ MH ZZ 1 AA 24Hr Panic PA ZZ PH ZZ 1 2A 24Hr Emergency non med...

Page 64: ...ed to one line should not exceed five 5 0 To be certain of the number of devices that you may connect to your line you may want to contact your local telephone company Equipment Maintenance Facility I...

Page 65: ...nces or passing traffic Audible warning devices however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or...

Page 66: ...Yes No identified Wireless Keys support Only the first 32 zones can be used as wireless zones PC5132 v3 X Yes Only the first 32 zones can be used as wireless zones PC5400 Printer DVACS Module v1 X to...

Reviews: