G e t t i n g S t a r t e d :
2 . 1 0 2 4 - H r A u x i l i a r y I n p u t W i r i n g ( P G M 2 )
7
NOTE:
See the Wiring Diagram Compatibility Chart for a list of
compatible 2-wire smoke detectors.
NOTE:
If PGM2 is programmed for 2-wire smoke support, the
connector JP1 on the main board must be removed.
NOTE:
2-wire smoke detectors are not supported on the 50/50
version of the panel.
2.10 24-Hr Auxiliary Input Wiring (PGM2)
If PGM2 has been programmed for 24-hour operation, the
zone must be wired according to the following diagram:
NOTE:
If PGM2 is pro-
grammed for 24-hr auxil-
iary input support, the
connector JP1 on the main
board must be removed.
2.11Zone Wiring
For a complete description of the operation of all zone types,
please refer to 5.2
“Zone Programming”
.
There are several different ways in which zones may be wired,
depending on which programming options have been
selected. The panel can be programmed to supervise nor-
mally closed, end of line, or double end of line loops. Please
refer to the following diagrams to study each type of individu-
ally supervised zone wiring.
NOTE:
Any zone programmed for fire or 24 hour supervisory
must be wired with a single end of line (EOL) resistor regard-
less of the type of zone wiring supervision selected for the
panel (section [013]: [1] -[2]). see 5.2
“Zone Programming”
NOTE:
If you change the zone supervision options from DEOL
to EOL or from NC to DEOL (section [013], options [1] or [2]),
you should power down the system completely, and then
power it back up. If you do not, the zones may not work cor-
rectly.
Normally Closed (NC) Loops
To enable normally closed loops, programming section [013],
option [1] must be ON.
NOTE:
This option should only be selected if normally closed
(NC) detection devices or contacts are being used.
Single End Of Line (EOL) Resistors (5600
Ω
)
To enable panel detection of single end of line resistors, pro-
gramming section [013], Options [1] and [2] must be OFF.
NOTE:
This option should be selected if either normally closed
(NC) or normally open (NO) detection devices or contacts are
being used.
Double End of Line (DEOL) Resistors
Double end of line resistors allow the panel to determine if the
zone is in alarm, tampered or faulted.
To enable panel detection of double end of line resistors, pro-
gramming section [013], option [1] must be OFF and option
[2] must be ON.
NOTE:
If the double EOL supervision option is enabled, all
hardwire zones on the main panel must be wired for double
EOL resistors, except for fire and 24 Hour supervisory zones.
NOTE:
Do not wire DEOL resistors on keypad zones.
NOTE:
Do not use DEOL resistors for fire zones or 24 hour
supervisory zones. Do not wire fire zones to keypad zone ter-
minals if the DEOL supervision option is selected.
NOTE:
This option can only be selected if normally closed
(NC) detection devices or contacts are being used.
NOTE:
Only one NC contact can be connected to each zone.
Wiring multiple detection devices or contacts on a single loop
is not allowed.
The following chart shows zone status under certain conditions:
Loop Resistance
Loop Status
0
Ω
(shorted wire, loop shorted)
Fault
5600
Ω
(contact closed)
Secure
Infinite (broken wire, loop open)
Tamper
11200
Ω
(contact open)
Violated
End-of-Line Resistors. . . . . . . . . . . . . . . . . .Section [013]: [1]
Double End-of-Line Resistors . . . . . . . . . . .Section [013]: [2]
ANY Z
TERMINAL
ANY COM
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL