44

Table2: Contact ID Zone Alarm/Restoral Event 
Codes (as per ADEMCO):

Program any of these codes for zone alarms/restorals when using
the standard (non-automatic) Contact ID reporting format.

Table 3: SIA Format Automatic Zone 
Alarm/Restoral Codes

Section #

Reporting Code

Code Sent When...

Dialer 

Direction*

Automatic 

Contact ID 

Codes

SIA Auto Rep 

Codes**

[349-350]

AC Line Trouble/Rest.

AC power to control panel is disconnected or inter-
rupted/AC power restored (both codes follow AC Failure 
Comm. Delay.)

MA/R

(3) A1

AT-00/AR-00

[349-350]

Main Bell Trouble/Rest.

open circuit detected across bell terminals/bell circuit 
closed

MA/R

(3) 21

UT-99/UJ-99

[349-350]

Fire Trouble/Rest.

a trouble occurs/restores on a fire zone

MA/R

(3) 73

FT-00/FJ-00

[349-350]

Auxiliary Power Trouble/
Rest.

aux voltage supply trouble/restoral

MA/R

(3) AA

YP-00/YQ-00

[349]

TLM Failure

telephone line monitoring trouble (sent via LINKS. Do 
not program if LINKS not used)

MA/R

(3) 51

LT-00

[350]

TLM Restore

Telephone line trouble restoral

MA/R

(3) 51

LR-00

[349-350]

Gen System Trouble/Rest.

“Service Required” trouble occurs (view troubles using 
[*][2])/trouble restored

MA/R

(3) 33

ET-00/ER-00

[349-350]

Gen System Supervisory 
Trouble/Rest.

control panel loses/restores communications with  mod-
ule(s) connected to the Keybus

MA/R

(3) 33

ET-00/ER-00

[351]

Line 1 or 2 FTC Restoral

control panel has restored communications to central 
station on line 1 or 2 (after FTC)

MA/R

(3) 54

YK-00

[351]

Event Buffer is 75% Full

event buffer is almost full since last upload

MA/R

(6) 23

JL-00

[351]

DLS Lead In

downloading session start

MA/R

(4) 11

RB-00

[351]

DLS Lead Out

downloading session complete

MA/R

(4) 12

RS-00

[351]

Zone Fault/Rest.

one or more zones have faults/restored

MA/R

(3) 72

UT-00/UJ-00

[351]

Delinquency

programmed amount of time (days or hours) for delin-
quency has expired without zone activity or without sys-
tem being armed

MA/R

(4) 54***

CD-00

[352]

Periodic Test

periodic system test transmission  

T

(6) A2

RP-00

[352]

System Test

[*][6] bell/communications test

T

(6) A1

RX-00

[352]

LINKS Test

LINKS test transmission

T

(6) A3

TX-00

[353]

Wireless Device Low Bat-
tery Trouble/Rest.

wireless zones (WLS904(P), WLS906, WLS907T,
WLS925L); handheld keypads (WLS910); wireless keys
(WLS919) have low battery/all low batteries restored

MA/R

(3) 84

XT-00/XR-00

* A/R = Alarms/Restorals; T/R = Tampers/Restorals; O/C = Openings/Closings; MA/R = Miscellaneous Alarms/Restorals; T = Test Transmissions

** UU = User Number (user 01-42); ZZ = Zone Number (01-32)

***Program the “Fail to Close” event code [(4)54] to report either closing or activity delinquency.

Make sure your central station is aware of the application of this reporting code.

Medical Alarms 

(1)34  Entry / Exit

(1)AA  Medical

(1)35  Day / Night

(1)A1  Pendant Transmitter

(1)36  Outdoor

(1)A2  Fail to Report In

(1)37  Tamper

Fire Alarms

(1)38  Near Alarm

(1)1A  Fire Alarm

General Alarms

(1)11  Smoke

(1)4A  General Alarm

(1)12  Combustion

(1)43  Exp. Module Failure

(1)13  Water Flow

(1)44  Sensor Tamper

(1)14  Heat

(1)45  Module Tamper

(1)15  Pull Station

(1)4A  Cross Zone Police Code

(1)16  Duct

24 Hour Non-Burglary

(1)17  Flame

(1)5A  24 Hour non-Burg

(1)18  Near Alarm

(1)51  Gas Detected

Panic Alarms

(1)52  Refrigeration

(1)2A  Panic

(1)53  Loss of Heat

(1)21  Duress

(1)54  Water Leakage

(1)22  Silent

(1)55  Foil Break

(1)23  Audible 

(1)56  Day Trouble

Burglar Alarms

(1)57  Low Bottled Gas level

(1)3A  Burglary

(1)58  High Temp

(1)31  Perimeter

(1)59  Low Temp

(1)32  Interior

(1)61  Loss of Air Flow

(1)33  24 Hour

Zone Definition

SIA Auto Rep 

Codes*

Zone Alm/Rest.

Delay, Instant, Interior, Delay 
Stay/Away, Interior Stay/Away, 
24Hr Burg.

BA-ZZ/BH-ZZ

Standard 24Hr Fire, Delayed 
24Hr  Fire

FA-ZZ/FH-ZZ

24Hr Supervisory

US-ZZ/UR-ZZ

24Hr Supervisory Buzzer

UA-ZZ/UH-ZZ

24Hr Sprinkler

SA-ZZ/SH-ZZ

24Hr Gas

GA-ZZ/GH-ZZ

24Hr Heat

KA-ZZ/KH-ZZ

24Hr Medical

MA-ZZ/MH-ZZ

24Hr Emergency (non-medical)

QA-ZZ/QH-ZZ

24Hr Waterflow

WA-ZZ/WH-ZZ

24Hr Freeze

ZA-ZZ/ZH-ZZ

24Hr Holdup

HA-ZZ/HH-ZZ

24Hr Panic

PA-ZZ/PH-ZZ

Latching 24Hr 

BA-ZZ/BH-ZZ

* ZZ = zones 01-32

Summary of Contents for Power632

Page 1: ...function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read This panel will not operate if installed outside of North America See sectio...

Page 2: ...a period of twelve months from the date of purchase the product shall be free of defects in materials and workmanship under normal use During the warranty period Digital Security Controls Ltd shall a...

Page 3: ...booklet is available from the U S Gov ernment Printing Office Washington D C 20402 Stock 004 000 00345 4 IMPORTANT INFORMATION This equipment complies with Part 68 of the FCC Rules On the side of this...

Page 4: ...ii PC1555MX Wiring Diagram LCD5500Z LCD5501Z PC1555RKZ LCD5501Z32 PC5502Z2 PC5506 PC5508Z PC5516Z PC5532Z SL 8...

Page 5: ...imline 8 zone LED keypad All keypads have five programmable function keys Connect up to eight keypads 4 wire Quad connection to Keybus Built in piezoelectric buzzer Digital Communicator Specifications...

Page 6: ...control Each output is individually programmable see 5 11 PGM Output Options See PC5208 Installation Instructions Sheet Escort5580 TC Module This Escort5580 TC module will turn any touch tone phone i...

Page 7: ...sions 208mm x 115mm x 18mm 8 2 x 4 5 x 0 7 approxi mately 1 3 Out of the Box Please verify that the following components are included in your system one main control cabinet one PC1555MX main control...

Page 8: ...ramming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as programmed 2 2 T...

Page 9: ...ot connect the alarm panel communicator to telephone lines intended for use with a fax machine These lines may incorporate a voice filter which disconnects the line if anything other than fax signals...

Page 10: ...twice to exit installer programming After assigning all keypads perform a supervisory reset by entering section 902 in Installer s Programming The panel will now supervise all assigned keypads and enr...

Page 11: ...osed NC Loops To enable normally closed loops programming section 013 option 1 must be ON NOTE This option should only be selected if normally closed NC detection devices or contacts are being used Si...

Page 12: ...e terminals on the keypad circuit board Connect the four Keybus wires from the control panel the red wire to R the black to B the yellow to Y and the green to G To connect the zone run one wire to the...

Page 13: ...me every day if it is in the disarmed condition In order for the auto arm function to work properly you must program the cor rect time of day For programming the clock and auto arm times see 6 User Fu...

Page 14: ...then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or annunciated 2 AC Failure AC power is no longer being supplie...

Page 15: ...l while other codes are silent To do this enable attribute 7 on all access codes associated with wireless keys NOTE If you enable the Bell Squawk on Arming Disarming section 014 option 1 the bell will...

Page 16: ...Delay 3 5 Function Keys There are five function keys on each keypad labelled Stay Away Chime Reset and Exit Each of these keys is pro grammed by default to perform one of the functions described belo...

Page 17: ...n 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For Future Use 21 7 4 Command Output Option 4 A valid access code may need to be entered 3 6 Features Available for t...

Page 18: ...the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4 2 Programming D...

Page 19: ...wed from an LED key pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a...

Page 20: ...pendently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will cause an instant alarm if it is violated when the panel is armed Typically this zone is used for window...

Page 21: ...to a LINKS Answer zone see 2 12 LINKS Zone Wiring Refer to the LINKS1000 Installation Manual for more information NOTE Do not wire LINKS Answer zones on keypad zone ter minals 25 Interior Delay Zone...

Page 22: ...Tone Detection Section 701 6 Maximum Dialing Attempts Section 160 Post Dial Wait for Handshake Section 161 5 6 Communicator Account Numbers The account number is used by the central station to distin...

Page 23: ...from transmitting an AC Failure Trouble Alarm reporting code during short power outages the panel will not send the signal unless AC power is lost for the amount of time programmed for the AC Failure...

Page 24: ...he panel will operate as follows 1 If an event s reporting code is programmed as 00 or FF the panel will not attempt to call the central station 2 If the reporting code for an event is programmed as a...

Page 25: ...er 8 Installer s Code 499 Installer s Code 499 All key pads will be busy for the duration of the PC Link connection The status LEDs will display the current system status on the keypad where the PC Li...

Page 26: ...ill deacti vate if a user enters a valid access code while the bell cut off timer is counting down The output will also deactivate if someone arms the system after the bell cut off has expired This ou...

Page 27: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the Programming Worksheets for a list of the default settings for each PGM out put type Be carefu...

Page 28: ...e times to verify activation The panel will beep the keypad ten times rapidly when a kissoff is received to verify communication to the central station If the P key is pressed and held for two seconds...

Page 29: ...go into alarm If there was an alarm during the armed period the keypad will pulse for the entire entry delay to warn the user of the previous alarm For commercial applications Bell Squawk on Entry Del...

Page 30: ...elephone numbers as a redundant backup to the land line communicator where the panel will call using the land line and the LINKS A LINKS Preamble is programmable for each telephone num ber in the even...

Page 31: ...pro grammed Refer to your PC5132 v3 0 PC5102 v1 0 Installation Manual for more information NOTE The LINKS2X50 module has not been investigated by UL Restore Alternative Communicator LINKS2X50 Skyroute...

Page 32: ...I PC5400 Serial Printer Module I________________________________________________________________________________________________________________I LINKS1000 Cellular Communicator I_____________________...

Page 33: ...___I_____I_____I_____I_____I_____I_____I_____I_____I I_____I_____I I_____II_____II_____II_____II_____II_____II_____II_____I I_____I_____I_____I_____I_____I_____I Zone 17 I_____I_____I_____I_____I_____...

Page 34: ...talled to use 24 hour Buzzer zones NOTE Keypad zones are assigned in section 020 Zone Attributes are assigned in sections 101 132 Zone assign ment is in sections 202 205 001 Zone 1 8 Definitions Secti...

Page 35: ...___I_______I_______I Exit Delay in seconds Section 5 18 Entry Exit Delay Options 004 I_______I_______I_______I Bell Cut off in minutes Section 5 13 Bell 006 Installer s Code Section 4 1 Installer s Pr...

Page 36: ...ors 2 11 ON I________I 3 Panel Shows All Troubles When Armed Panel Shows Only Fire Troubles When Armed 3 4 OFF I________I 4 Tampers Faults Do Not Show As Open Tampers Faults Show As Open 3 4 OFF I____...

Page 37: ...pers Disabled 5 25 017 Fifth System Option Code Default Option ON Off Section ON I________I 1 WLS Key Does Not Use Access Codes WLS Key Uses Access Codes 5 17 OFF I________I 2 7 For Future Use OFF I__...

Page 38: ...________I I________ I________ I________ I________ I________ I________ I________I 113 13 I________I I________ I________ I________ I________ I________ I________ I________I 114 14 I________I I________ I_...

Page 39: ...________ I________I 131 31 I________I I________ I________ I________ I________ I________ I________ I________I 132 32 I________I I________ I________ I________ I________ I________ I________ I________I Re...

Page 40: ..._____I_______I_______I Valid entries are 001 015 attempts do not enter 000 161 Post Dial Wait for Handshake All Formats Section 5 5 Communicator Dialing Default 040 I_______I_______I_______I Valid ent...

Page 41: ..._I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 325 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone16 I_______I_______I I____...

Page 42: ...______I_______I I_______I_______I 343 Miscellaneous Closing Arming Reporting Codes Section 5 8 Communicator Reporting Codes Appendix A I_______I_______I 1 Closing by Duress Code 33 I_______I_______I 5...

Page 43: ...ion 5 8 Communicator Reporting Codes Appendix A I_______I_______I 1 Wireless Device Low Battery Alarm I_______I_______I 2 Wireless Device Low Battery Restore 360 Communicator Format Options Section 5...

Page 44: ...ay 001 255 seconds 5 15 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 1...

Page 45: ...Downloading Default Option ON Off OFF I_______I 1 Answering machine double call enabled Answering machine double call disabled ON I_______I 2 User Can Enable DLS Window User Cannot Enable DLS Window O...

Page 46: ...eypad LCD Keypad Bell Buzzer Good Light 1 ON Steady GOOD 1 Beep Squawk Bad Light 3 ON Steady BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 29 Installer s Lockout 991 Installer Lockout Dis...

Page 47: ...sion over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm two zones on the same partition go into alarm during any given armed...

Page 48: ...d MA R 4 54 CD 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wirel...

Page 49: ...e labels on page 29 33 Fire Alarm Label 14 Characters Default Fire Zone I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I 34 System Label 14 Characters Default Syst...

Page 50: ...I_______I 2 A uxiliary Keys Enabled A uxiliary Keys Disabled ON I_______I 3 P anic Keys Enabled P anic Keys Disabled OFF I_______I 4 8 For Future Use 65 Fourth User Display Mask Default Option ON OFF...

Page 51: ...abled Closing confirmation must be enabled The control panel must be in the Attack Resistant Enclosure DSC Model CMC 1 PC4050CAR PC4004C Swinger shutdown must be disabled All Commercial Installations...

Page 52: ...s Links2450 Yes Not investigated by UL PC 16 Out No PC1500RK No PC1555RKZ Yes PC5102 Yes PC5108 No PC5108L No PC5132 v1 X Yes No support for wireless keys pendants or handheld keypads PC5132 v2 X Yes...

Reviews: