14
7.2.5 Output Computer Alarm Messages to the
Computer: LC-FA-06-XX
The LC-FA-06-XX command will send the specified number
of computer alarm messages to the computer. “XX” should
be a hexadecimal number from 01 to FE to indicate a number
of events from 1 to 254.
This command provides a means of manually transferring
events to the computer. If the computer goes off-line, the
CPM2 will record any events in its own buffer. When the
computer returns on-line, the CPM2 will automatically send
the computer any alarm messages that were received while
the computer was off-line.
7.3 Shutdown Line Card
Communication with CPM2: LC-FB
The LC-FB command will shut down communications between
the Line Card specified at “LC” and the CPM2. Note that
this command does not require an Option or Code number
to be entered; simply enter the number of the Line Card to
be shut down, the command FB, and then press the CPM2
[Escape] button.
The CPM2 will record the shut down by sending messages
to the printer and the computer:
Printer: -L01-Inc.Resp. 11:57:58-15/01
Computer: 1011 0000 A F1
This warning message will also be displayed on the Line
Card display:
L01-Digital Rec
LnCard Shutdown!
7.4 Reactivate Line Card Command:
LC-FC
The LC-FC command will reactivate a Line Card that was
shut down using the LC-FB command. Note that this command
does not require an Option or Code number to be entered;
simply enter the number of the Line Card to be reactivated,
the command FC, and then press the CPM2 [Escape] button.
7.5 Line Card Buffer Command:
LC-FE-XX-XX
The FE command is used to access the Line Card buffers.
The following functions may be performed:
7.5.1 Erase Alarm Printer/Computer Messages:
LC-FE-00-00
Ensure that a copy of the printer and computer alarms exists
before using this command. This command erases all
computer and printer alarm messages and Caller Identification
messages in the Line Card’s memory.
7.5.2 Software Reset: LC-FE-02-02
This command will reset the Line Card.
7.5.3 Backup Current Line Card Configuration:
LC-FE-03-03
When the Line Card has been configurated, the programming
changes can be recorded as a “back up” program. The
“back up” configuration may be later used to restore the
Line Card’s configuration after temporary changes are made.
To store the present Line Card configuration, enter the LC-
FE-03-03 command.
7.5.4 Install Backup Configuration as Current Line Card
Configuration: LC-FE-04-04
If the Line Card configuration is temporarily changed (for
example, to overcome a temporary problem or for
experimentation), the configuration stored using the LC-FA-
03-03 command may be restored.
To restore the “back up” configuration, enter the LC-FE-04-
04 command.
Section 7
firealarmresources.com