Section 4: Programming Options
Note:
Domain Name Service (DNS) programming is not per-
mitted in UL/ULC listed systems
Note:
To use the panel’s alternate DNS server, the option
LAN/WLAN Obtain IP Address must be set to Static IP
address.
Default:
000.000.000.000
Valid range:
000.000.000.000 to 255.255.255.255
WiFi Country Code
This option is used to select the country of operation for the
alarm system.
Default:
CA (Canada)
Valid range:
US, AU, CA, UK, FR, SE, IL, None
WLAN SSID
This section is used to program a network name (unique
identifier) for the panel.
Default:
None
Valid range:
Alphanumeric
WLAN Client Control
This option is used to control WiFi client mode.
Default:
Enabled
Valid range:
Enabled/Disabled
WLAN Security Type
This option is used to select which encryption protocol the
system uses to secure the wireless network.
Default:
WPA2 PSK AES
Valid range:
WPA PSK TKIP
WPA PSK AES
WPA PSK TKIP AES
WPA2 PSK TKIP
WPA2 PSK AES
WPA2 PSK TKIP AES
MIXED MODE TKIP
MIXED MODE AES
MIXED MODE TKIP AES
WLAN Security Key
This section is used to program a password for the Wi-Fi net-
work.
Default:
None
Valid range:
32 character ACCII
Panel's Cellular Public APN
This section is used to program the Access Point Name of
the network used for cellular-data connectivity.
Default:
Blank
Valid range:
32 ASCII characters or Null
Panel's Cellular Login User Name
This section is used to program a user name for cellular net-
work connection.
Default:
Blank
Valid range:
32 ASCII characters or Null
Panel's Cellular Login Password
This section is used to program a user password for cellular
network connection.
Default:
Blank
Valid range:
32 ASCII characters or Null
Time Zone
This option defines the time zone that the alarm system will
operate in. From the list of valid entries, locate and select the
appropriate time zone.
Default: US Eastern
Valid
range:
US-Alaska, US-Aleutian, US-Arizona, US-Central, US-
Eastern, US-Hawaii, US-Indiana-East, US-Indiana-Starke,
US-Michigan, US-Mountain, US-Pacific, US-Samoa, CA-
Atlantic, CA-Central, CA-Eastern, CA-Mountain, CA-New-
foundland, CA-Pacific, CA-Saskatchewan, CA-Saskat-
chewan-East, CA-Yukon
4.3 Central Monitoring Station
Programming Options
The following section provides descriptions of all pro-
gramming options for communications between the iotega
and the central monitoring station.
Communication Path
Use this option to select the method by which the panel com-
municates to the central monitoring station. Choose one of
the following:
None: The system does not communicate to the central mon-
itoring station via Ethernet or Cellular.
Ethernet: The system communicates to the central mon-
itoring station via Ethernet connection only.
- 23 -