Specification
16
3.8.4 MAGNETIC PICKUP
Type
Differential input
Minimum Voltage
0.5V RMS
Max Common Mode Voltage
±2V
Maximum Voltage
Clamped to ±70V by transient suppressers, dissipation not to
exceed1W.
Maximum Frequency
10,000 Hz
Resolution
6.25 RPM
Accuracy
±25 RPM
Flywheel Teeth
10 to 500
NOTE: DSE can supply a suitable magnetic pickup device, available in two body thread
lengths:
DSE Part number 020-012 - Magnetic Pickup probe 5/8 UNF 2½” thread length
DSE Part number 020-013 - Magnetic Pickup probe 5/8 UNF 4” thread length
Magnetic Pickup devices can often be ‘shared’ between two or more devices. For example, one
device can often supply the signal to both the DSE module and the engine governor. The possibility
of this depends upon the amount of current that the magnetic pickup can supply.
3.9 OUTPUTS
3.9.1 DC OUTPUTS A & B (FUEL & START)
Type
Normally used as Fuel & Start outputs.
Fully configurable for other purposes if the module is configured to control an
electronic engine.
Rating
10A resistive for 10secs, 5A resistive continuous at plant supply.
3.9.2 CONFIGURABLE VOLT-FREE OUTPUTS C & D
Type
Normally used for load switching control
Fully configurable volt-free relays. One normally open and one normal closed.
Rating
8A resistive at 250 V AC
3.9.3 CONFIGURABLE DC OUTPUTS E, F, G & H
Type
Fully configurable, supplied from DC supply terminal 2.
Rating
2A resistive continuous at plant supply.
Summary of Contents for DSE7110 MKII
Page 34: ...Installation 34 4 2 1 DSE7110 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 35: ...Installation 35 4 2 2 DSE7120 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 36: ...Installation 36 4 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 4 3 1 GENERATOR ...
Page 37: ...Installation 37 4 3 2 MAINS DSE7120 MKII ONLY ...