Description Of Controls
52
Icon
Fault
Description
Generator Under
Frequency
The generator output frequency has fallen below the pre-set alarm
setting after the Safety On timer has expired.
Generator Over
Frequency
The generator output frequency has risen above the pre-set alarm
setting.
Delayed Over Current
The measured current has risen above the configured trip level for
a configured duration.
kW Overload
The measured kW has risen above the configured trip level for a
configured duration.
CAN ECU Fault
The engine ECU has detected an alarm – CHECK ENGINE LIGHT
Contact Engine Manufacturer for support.
CAN Data Fail
The module is configured for CAN operation and does not detect
data on the engine Can data link.
Emergency Stop
The emergency stop button has been depressed. This failsafe
(normally closed to emergency stop) input and immediately stops
the set should the signal be removed.
Oil Sender Open
Circuit
The oil pressure sensor has been detected as being open circuit.
Coolant Temperature
Sender Open Circuit
The coolant temperature sensor has been detected as being open
circuit.
Oil Filter
Maintenance Alarm
Maintenance due for oil filter.
Air Filter
Maintenance Alarm
Maintenance due for air filter
Fuel Filter
Maintenance Alarm
Maintenance due for fuel filter.
Summary of Contents for DSE7110 MKII
Page 34: ...Installation 34 4 2 1 DSE7110 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 35: ...Installation 35 4 2 2 DSE7120 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 36: ...Installation 36 4 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 4 3 1 GENERATOR ...
Page 37: ...Installation 37 4 3 2 MAINS DSE7120 MKII ONLY ...