Operation
71
6.6 MAINTENANCE ALARM
Depending upon module configuration one or more levels of engine maintenance alarm may occur
based upon a configurable schedule.
Example 1
Screen capture from DSE Configuration
Suite Software showing the configuration
of the Maintenance Alarm for Oil, Air
and Fuel.
When activated, the maintenance alarm
can be either a
warning
(set continues
to run) or
shutdown
(running the set is
not possible).
Resetting the maintenance alarm is
normally actioned by the site service
engineer after performing the required
maintenance.
The method of reset is either by:
•
Activating an input that has been
configured to Maintenance Reset
Alarm x, where x is the type of
maintenance alarm (Air, Fuel or Oil).
•
Pressing the maintenance reset
button in the DSE Configuration Suite, Maintenance section.
•
Pressing and holding the
Stop/Reset Mode
button for 10 seconds on the desired Maintenance
Alarm status page. This can be protected by a PIN number.
Example 2
Screen capture from DSE Configuration Suite
Software showing the configuration of a digital
input for Maintenance Reset Alarm Air.
Example 3
Screen capture from DSE Configuration Suite
Software showing the Maintenance Alarm
Reset ‘button’ in the DSE Configuration Suite
SCADA | MAINTENANCE section.
Summary of Contents for DSE7110 MKII
Page 34: ...Installation 34 4 2 1 DSE7110 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 35: ...Installation 35 4 2 2 DSE7120 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 36: ...Installation 36 4 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 4 3 1 GENERATOR ...
Page 37: ...Installation 37 4 3 2 MAINS DSE7120 MKII ONLY ...