SPECIFICATIONS
NOTE: This document is intended as a ‘quick start’ guide only. For full
operating instructions and specifications, refer to DSE publication:
057-255 DSE9462 Operator Manual.
Description
Specification
Connection Type
Cage clamp terminals
Min Cable Size Accepted in Terminal
(Battery Connection)
0.08 mm² (AWG 28)
Max Cable Size Accepted in Terminal
(Battery Connection)
4.0 mm² (AWG 12)
Strip Length (Battery Connection)
8 mm to 9 mm
(0.31 “ to 0.35 “)
Min Cable Size Accepted in Terminal
(Other Connections)
0.08 mm² (AWG 28)
Max Cable Size Accepted in Terminal
(Other Connections)
2.0 mm² (AWG 14)
Strip Length (Other Connections)
7 mm to 8 mm
(0.28 “ to 0.31 “)
Recommended AC Fuse
230 V AC Input
110 V AC Input
10 A anti-surge
10 A anti-surge
MAINS SUPPLY CABLE
Connection
Cable Colour
L1
Brown
Neutral
Blue
Earth
Green and Yellow
STATUS LEDS
Each output has its own dedicated LED to show charge status.
Status 1: Charge status of Output 1.
Status 2: Charge status of Output 2.
Condition
Status LED
Output Not Charging (Due to Fault or Charger Off)
Off
Battery Detection Mode
Green Constant
Bulk (Boost) Charge in Progress
Yellow Constant
Absorption Charge in Progress
Yellow Flashing
Float Charge in Progress
Green Constant
Storage Charge in Progress
Green Flashing
FAULT LEDS
Two Fault LEDs, Fault 1 and Fault 2 are used to indicate faults. Output 1 and
Output 2 share these indications. Where two alarms are present at the same time,
the most critical is displayed.
Condition
LED
Fault 1
Fault 2
DC Over Volts Warning and Trip
DC Under Volts Warning
Battery Detection Warning
DC Over Current
Battery Reverse Polarity
Short Circuit Protection
Battery Detection Warning
Red Constant
Off
Input Fuse Failure
AC Under Voltage Warning and Trip
AC Over Volts Warning and Trip
DC Over Current Warning
Cable Voltage Drop Alarm
Red Flashing
Off
Battery Over Temperature Warning and Trip
Battery Temperature Sensor (PT1000) Fail
Ambient Over Temperature
Off
Red Constant
Battery Charger Failure
Red Constant
Red Constant
Battery Detection Mode - Battery Not Detected
Red Flashing
Red Flashing
DIMENSIONS AND MOUNTING
NOTE: The DSE battery charger is designed to be mounted with the
base to a vertical surface with the connection terminals at the bottom.
Description
Dimension
Case Dimensions
162 mm x 291 mm x 74 mm
(6.4 ” x 11.5 ” x 2.9”)
Mounting Holes Dimensions
Suitable for M5
(0.2 ” diameter)
Mounting Hole Spacing
95 mm x 279 mm
(3.7 ” x 11.0 ”)
Required Ventilation Spacing
100 mm (3.9 ”) air space around the battery charger.