SPECIFICATIONS 

 

NOTE: This document is intended as a ‘quick start’ guide only. For full 

operating instructions and specifications, refer to DSE publication:   
057-255   DSE9462 Operator Manual. 

 

Description 

Specification 

Connection Type 

Cage clamp terminals 

Min Cable Size Accepted in Terminal 
(Battery Connection) 

0.08 mm² (AWG 28) 

Max Cable Size Accepted in Terminal 
(Battery Connection) 

4.0 mm² (AWG 12) 

Strip Length (Battery Connection) 

8 mm to 9 mm 
(0.31 “ to 0.35 “) 

Min Cable Size Accepted in Terminal  
(Other Connections) 

0.08 mm² (AWG 28) 

Max Cable Size Accepted in Terminal  
(Other Connections) 

2.0 mm² (AWG 14) 

Strip Length (Other Connections) 

7 mm to 8 mm 
(0.28 “ to 0.31 “) 

Recommended AC Fuse  

230 V AC Input 

110 V  AC Input 

10 A anti-surge 

10 A anti-surge 

 
 

MAINS SUPPLY CABLE 

 

Connection 

Cable Colour 

L1 

Brown 

Neutral 

Blue 

Earth 

Green and Yellow 

 
 

STATUS LEDS 
 

Each output has its own dedicated LED to show charge status. 
Status 1: Charge status of Output 1. 
Status 2
: Charge status of Output 2. 
 

Condition 

Status LED 

Output Not Charging (Due to Fault or Charger Off) 

Off 

Battery Detection Mode 

Green Constant 

Bulk (Boost) Charge in Progress 

Yellow Constant 

Absorption Charge in Progress 

Yellow Flashing 

Float Charge in Progress 

Green Constant 

Storage Charge in Progress 

Green Flashing 

FAULT LEDS 

 
Two Fault LEDs, Fault 1 and Fault 2 are used to indicate faults. Output 1 and 
Output 2 share these indications. Where two alarms are present at the same time, 
the most critical is displayed. 
 

Condition 

LED

 

Fault 1 

Fault 2 

DC Over Volts Warning and Trip 
DC Under Volts Warning 
Battery Detection Warning 
DC Over Current 
Battery Reverse Polarity 
Short Circuit Protection 
Battery Detection Warning  

Red Constant 

Off 

Input Fuse Failure 
AC Under Voltage Warning and Trip 
AC Over Volts Warning and Trip 
DC Over Current Warning 
Cable Voltage Drop Alarm 

Red Flashing 

Off 

Battery Over Temperature Warning and Trip 
Battery Temperature Sensor (PT1000) Fail 
Ambient Over Temperature 

Off 

Red Constant 

Battery Charger Failure 

Red Constant 

Red Constant 

Battery Detection Mode - Battery Not Detected 

Red Flashing 

Red Flashing 

 
 
DIMENSIONS AND MOUNTING 

 

NOTE: The DSE battery charger is designed to be mounted with the 

base to a vertical surface with the connection terminals at the bottom. 

 

Description 

Dimension 

Case Dimensions 

162 mm  x 291 mm x 74 mm 
(6.4 ” x 11.5 ” x 2.9”) 

Mounting Holes Dimensions 

Suitable for M5 
(0.2 ” diameter) 

Mounting Hole Spacing 

95 mm x 279 mm 
(3.7 ” x 11.0 ”) 

Required Ventilation Spacing 

100 mm (3.9 ”) air space around the battery charger.  

 

 