Description Of Controls
Page 43 of 100
057-230 ISSUE: 1
4.3 CONTROL PUSH-BUTTONS
Icon
Description
Stop / Reset
Mode
This button places the module into its
Stop/Reset Mode
. This clears any alarm
conditions for which the triggering criteria have been removed. If the engine is
running and the module is put into Stop mode, the module automatically instructs
the generator to unload (
Close Generator
and
Delayed Load Output 1, 2, 3 & 4
become inactive (if used))
. The fuel supply de-energises and the engine comes to a
standstill. Should any form of
remote start signal
be present when in
Stop Mode
the
generator remains at rest
Manual Mode
This button places the module into its
Manual
Mode
. Once in
Manual
Mode
, the module responds to the
Start
button to start the
generator and run it off load.
To place the generator on load, use the
Transfer to Generator
button. The
module automatically instructs the changeover device to place the generator on
load
(‘Close Generator’
and Delayed Load Output 1, 2, 3 & 4 becomes active (if
used))
. To place the generator off load, use the
Transfer to Mains
or
Open
Generator
buttons. The module automatically instructs the changeover device
to place the generator off load
(Close Generator and Delayed Load Output 1, 2, 3 &
4 becomes inactive (if used))
. Additional digital inputs can be assigned to perform
these functions.
If the engine is running off-load in
Manual
Mode
and a remote start signal
becomes present, the module automatically instructs the changeover device to
place the generator on load
(‘Close Generator’ and ‘Delayed Load Output 1, 2, 3 &
4’ becomes active (if used))
. Upon removal of the
Remote Start Signal
, the
generator remains on load until either selection of the
Stop/Reset Mode
or
Auto Mode
.
For further details, please see
section entitled ‘Operation’ elsewhere in this manual.
Test Mode (DSE6020 MKII Only)
This button places the module into its
Test Mode
. Once in
Test Mode
, the
module responds to the
Start
button to start the generator and run it off load.
Once the set has started the set automatically be placed on load (
Close Generator
and
Delayed Load Output 1, 2, 3 & 4
become active in order from lowest to highest
(if used)).
For further details, please see section entitled ‘Operation’ elsewhere in this manual.