Operation
057-230 ISSUE: 1
Page 72 of 100
5.6 MAINTENANCE ALARM
Depending upon module configuration one or more levels of engine maintenance alarm may occur
based upon a configurable schedule.
Example 1
Screen capture from DSE Configuration
Suite Software showing the configuration
of the
Maintenance Alarm
for Oil, Air and
Fuel.
When activated, the maintenance alarm
can be either a
Warning
(set continues to
run) or
Shutdown
(running the set is not
possible).
Resetting the
Maintenance Alarm
is
normally actioned by the site service
engineer after performing the required
maintenance.
The method of reset is either by:
Activating an input that has been
configured to
Maintenance Reset
Alarm
x, where x is the type of
maintenance alarm (Air, Fuel or Oil).
Pressing the maintenance reset
button in the DSE Configuration Suite, Maintenance section.
Pressing and holding the
Stop/Reset Mode
button for 10 seconds on the desired Maintenance
Alarm status page. This can be protected by a PIN number.
Example 2
Screen capture from DSE Configuration Suite
Software showing the configuration of a digital
input for Maintenance Reset Alarm Air.
Example 3
Screen capture from DSE Configuration Suite
Software showing the Maintenance Alarm
Reset ‘button’ in the DSE Configuration Suite
SCADA | MAINTENANCE section.