Front Panel Configuration
Page 75 of 100
057-230 ISSUE: 1
6.1 ACCESSING THE FRONT PANEL CONFIGURATION EDITOR
NOTE: Pressing and holding the
or
navigation buttons provides the auto-repeat
functionality. Values can be changed quickly by holding the navigation buttons for a prolonged
period of time.
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The PIN number is not set by DSE when the module leaves the factory. If the
module has a PIN code set, this has been affected by your generator supplier who should be
contacted if you require the code. If the code has been ‘lost’ or ‘forgotten’, the module must
be returned to the DSE factory to have the module’s code removed. A charge is made for this
procedure.
NB - This procedure cannot be performed away from the DSE factory.
NOTE: The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
NOTE: More comprehensive module configuration is possible via PC configuration
software. For further details of module configuration, refer to DSE Publication: 057- 223
DSE60xx MKII Configuration Software Manual.
Press the
Stop/Reset Mode
and
Auto Mode
(
) buttons together to enter the
editor
mode.
Press the
(up) or
(down) navigation buttons to cycle through the front panel editor in
increments of 100.
Press the ( + ) or ( - ) navigation buttons to cycle through the front panel editor in increments of 1.
When viewing the parameter to be edited, press the
Auto Mode
(
) button and the value
begins to flash.
Press the ( + ) or ( - ) navigation buttons to adjust the value to the required setting.
Press the
Auto Mode
button the save the current value, the value ceases flashing.
Press and hold the
Auto Mode
button to save and exit the editor, the configuration icon
is
removed from the display.