DSE7110 & DSE7120 Operator Manual
23
5.5
CONTROLS
Stop / Reset
This button places the module into its Stop/Reset mode. This will clear any alarm conditions for which the
triggering criteria have been removed. If the engine is running and the module is in Stop mode, the module will
automatically instruct the changeover device to unload the generator (‘Close Generator’ becomes inactive (if
used)). The fuel supply de-energises and the engine comes to a standstill. Should a remote start signal be
present while operating in this mode, a remote start will not occur.
Once in the module will
Manual mode
This button places the module into its ‘Manual’ mode.
The module will respond to the start
button, start the engine, and run off load.
If the engine is running off-load in the Manual mode and a remote start signal becomes present, the module
will automatically instruct the changeover device to place the generator on load (‘Close Generator’ becomes
active (if used)). Upon removal of the remote start signal, the generator remains on load until either selection
of the ‘STOP/RESET’ or ‘AUTO’ modes.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this manual.
Auto Mode
This button places the module into its ‘Automatic’ mode. This mode allows the module to control the function
of the generator automatically. The module will monitor the remote start input and mains supply status and
once a start request is made, the set will be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the load from the generator and shut
the set down observing the stop delay timer and cooling timer as necessary. The module will then await the
next start event. For further details, please see the more detailed description of ‘Auto operation’ elsewhere in
this manual.
Start
This button is only active in STOP/RESET
or MANUAL
mode.
Pressing this button in manual or test mode will start the engine and run off load (manual) or on load (test).
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly configured and
fitted to a compatible engine ECU)
Lamp Test / Horn Reset
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test feature/
When correctly configured and fitted to a compatible engine ECU, pressing this button in STOP/RESET mode
after pressing the START
button (to power the ECU) will cancel any “passive” alarms on the engine ECU.
Transfer to generator
Allows the operator to transfer the load to the generator (when in Manual mode only)
On DSE7120, the mains load switch opens first (if not already open).
Open generator (DSE7110 only)
Allows the operator to open the generator (when in Manual mode only)
Transfer to mains (DSE7120 only)
Allows the operator to transfer the load to the mains (when in Manual mode only)
On DSE7120, the generator load switch opens first (if not already open)
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in this manual.