4.3 ALTERNATIVE TOPOLOGIES
The DSE8610 controller is factory configured to connect to a 3 phase, 4 wire Star connected
alternator. This section details connections for alternative AC topologies. Ensure to configure the
DSE8610 controller to suit the required topology.
NOTE: Further details of module configuration are contained within the DSE8610 Series
configuration software manual (DSE part number 057-119)
4.3.1 SINGLE PHASE WITH RESTRICTED EARTH FAULT
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read
earth faults ‘after’ the CT only (Restricted to load / downstream of the CT)
Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults
‘before’ the CT only (Restricted to generator / upstream of the CT)