Description of Controls
61
CLOSE MAINS
This push button is used to control the closure of the mains load switching device and has two modes
of operation :
1. Synchronising is NOT enabled. Pressing this button when the mains is available off load and in
MANUAL mode, the bus load switch is opened and the mains load switch is closed. Further
presses of this button will have no effect.
2. Synchronising is enabled. Pressing this button when the mains is available and in MANUAL
mode, the 8660 controller, will volts match and synchronise with the Bus. The mains load switch
is then closed in parallel with the Bus.
NOTE: This button is only active in MANUAL mode.
NOTE: If the bus is live when the manual button is pressed, synchronising will take place
before the load switch is closed.
CLOSE BUS
This push button is used to control the closure of the bus load switching device and has two modes of
operation :
3. Synchronising is NOT enabled. Pressing this button when the bus is off load and in MANUAL
mode, the mains load switch is opened and the bus load switch is closed. Further presses of this
button will have no effect.
4. Synchronising is enabled. Pressing this button when the bus is live and in MANUAL mode, the
8660 controller, will volts match and synchronise with the Mains. The bus load switch is then
closed in parallel with the mains.
NOTE: This button is only active in MANUAL mode.
NOTE: If the bus is live when the manual button is pressed, synchronising will take place
before the load switch is closed.
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in this manual.