SECTION 2 – PREINSTALLATION
2-1 SITE PLANNING AND PREPARARTION
The DEFENDER is designed for installation indoors where it is protected from the
elements. The UPS can be installed in a variety of different environments including
computer rooms, offices, and industrial/process control locations. For the best
performance and reliability, temperature extremes should be avoided.
Listed below are the environmental specifications for the DEFENDER UPS SYSTEM.
Adequate clearance around the equipment should be provided for service access and
proper equipment cooling. The UPS must be protected from contact with water and
other liquids. If the UPS is installed in a small, enclosed area, provisions for additional
cooling may be necessary.
OPERATING ENVIRONMENT.
Provide an operating environment that meets the
following conditions:
o
AMBIENT TEMPERATURE 32
°
to 104
°
F
0
°
to 40
°
C
o
OPERATING ALTITUDE 2,286 M (7500 FT)
o
NON-OPERATING ALTITUDE up to 3,048 M (10,000 FT)
o
RELATIVE HUMIDITY
0% to 95% (non-condensing)
! WARNING ! BATTERY SHELF LIFE !
•
BATTERY SHELF LIFE, WHEN STORED UNDER TEMERATURE CONDITIONS of
66
°
F ~ 77
°
F, is FOUR (4) MONTHS MAXIMUM AFTER THE SHIP DATE.
•
BATTERY MUST BE RECHARGED FOR EIGHT HOURS AFTER INSTALLATION
FOR THE FULL BACKUP TIME TO BE AVAILABLE.