The
History Log
is used to record certain events that reflect the status and operating
mode of the unit.
There are 64 lines (00 through 63).
It is read by holding down the
Alarm Scan
button. Each time the button is pressed, the
log is read sequentially with the most recent event being displayed first. After 00 is
displayed, the system will cycle around to 63.
After 64 events are logged, the system will start recording again at 00.
Code Message
Description
00
00
blank – used in clearing Alarm History
01
alarm clr
Alarm History has been cleared
02
Phase SEQ
Input phase sequence has caused a fault and must be changed
04
Input OV
Input voltage has gone over fault limit
05
Input UV
Input voltage has gone below fault limit
07
Input CONT
System has failed to detect closure of the Input Contactor
08
Output Hi V
Output voltage has gone over fault limit
09
Output Lo V
Output voltage has gone below fault limit
10
Output O Frq
Output frequency has gone over fault limit
11
Output U Frq
Output frequency has gone below fault limit
12
Phase FLT
Input phase sequence fault has not been corrected and system has timed
out
13
Invrtr. FLT
a hardware fault has been detected by the inverter control board (IGBT
PCBA); caused by IGBT failure, unexpected power on reset, or DC Bus
over voltage
14
DC Bus OV
DC Bus has gone over fault limit
15
DC Bus UV
DC Bus has gone below fault limit
16
Input O Frq
Input frequency has gone over fault limit
17
Input U Frq
Input frequency has gone below fault limit
18
RECT off
Rectifier has shut off unexpectedly
20
Invrt. O frq
Inverter frequency has gone over fault limit
21
Invrt. U Frq
Inverter frequency has gone below fault limit
22
ISBS open
Inverter Static Bypass Switch has not engaged and system has timed out
23
USBS fault
Utility Static Bypass Switch has failed test
24
USBS short
Utility Static Bypass Switch failure, output voltage still detected after off
command was issued
26
Output OVL
Output Current has gone over fault limit
28
Estop OPEN
Emergency Stop option enabled during system power-up
35
UPS abort
System faults have caused system to switch to bypass
36
Normal run
Automated system test concluded
37
BATT test
Automated system test initiated (15 minute rectifier shutoff and battery
run)
38
Inv start
Inverter has been started and matched with utility voltage
40
NMI trap
NMI button on processor board has been pressed, date and time marker
41
STKUF trap
Software Stack underflow detected
42
STKOF trap
Software Stack overflow detected
43
WDTMR trap
Software has detected a Watchdog timer overflow