The gate opens but will not
close.
The primary supply has failed
and the unit is running on
battery reserve with the
condominium/loop option
selected and it has reached its
low battery limit (9.5 Volt).
Safety infra-red beams are
obstructed or the beams
equipment/cabling are faulty
or incorrectly wired.
Check the household main
supply, the transformer or
PSU and all related cabling.
Clear obstruction, repair or
replace safety infra-red beams
equipment/cable, fix incorrect
wiring connections.
The gate when closing stops
and reverses or when
opening stops.
OR
Gate runs a short distance
and stops.
The unit is sensing an
obstruction
The infra-red beam has been
triggered.
Another trigger has been
received by the control card.
Encoder is faulty.
Clear obstruction or adjust
load sensing.
Clear obstruction.
Check with other operators on
the system.
Turn ring magnet on the motor
by hand: if no activity on the
encoder LED, contact
supplier. (Check that the PCB
is fitted correctly)
Gate does not remain open.
Auto close has been activated.
Another user has triggered the
unit.
Condominium/loop and or
Pirac mode has been activated.
(Dipswitch 4 or 5)
De-activate auto close or use
auto close override.
Check with other operators on
the system.
De-activate condominium /
loop mode and or Pirac mode.
When the beam input is
triggered, the gate stops and
closes during opening cycles.
When the gate auto opens.
If the gate on programming
does not run in slow speed.
P.I.R.A.C. mode, Dipswitch 5
has been activated.
The motor direction is
incorrectly selected.
The MOS-FET on the PCB is
blown or faulty.
De-activate P.I.R.A.C. mode
Select Dipswitch 2 correctly.
Replace the PCB.