10
ENGLISH
L2003212 Installation guide for DucoBox Energy Comfort (Plus) (Revision A | 18.10.2022)
04
Wiring
The DucoBox Energy Comfort (Plus) is able to communicate with slave components via a wireless (RF) or wired link� Both types of
communication can be combined in one system�
Communication with non-DUCO components is possible via the Switch Sensor or one of the connections on the optional Communi-
04.A
Wiring diagram
RF
24 VDC A B GND
B
A
GND
User controller
RF
230 VAC
User controller
POWER
SUPPLY
Max. of 50 components of which no more than 25 RF
RF obstacle-free zone (at least 30 cm)
Min
0,75 mm²
230 VAC
24 VDC
Duco Reference*
POWER
SUPPLY
24 VDC
230 VAC
Duco Wired
GND
B A
* Connecting a Power Supply to the DucoBox's 230VAC connection can only be done with a Power Supply tested and approved by
DUCO� Any references other than those offered by DUCO will void the guarantee of proper operation�
04.B
Mounting external power supply
For types D225 and D325
D225-D325: Mount the junction box with the transformer on
the unit�
D225-D325: Mounted junction box with transformer
1
2
Colours
230 VAC
brown + blue
24 VDC
brown + white
A
yellow
B
green
GND
grey