Calibrating flow rates
The DucoBox Energy Comfort (Plus) calibration mode can be activated using the display menu�
IMPORTANT, BEFORE CALIBRATING
Close all windows and doors. Ensure that all duct openings in the DucoBox Energy Comfort (Plus) are fully closed
and that the DucoBox Energy Comfort (Plus) cover is closed! Avoid air leaks in the ventilation ducts. Open all inte-
rior doors between the various zones.
Calibrating the DucoBox Energy Comfort (Plus)
1
Activate advanced mode:
• Scroll down to
ADVANCED
and press enter�
• Enter the installer’s code
9876
and press enter�
Calibrating
supply
vents
2
Scroll down to
CALIBRATION
→
WIZARD
and press enter� The DucoBox Energy Comfort
(Plus) calibration mode starts up� Do not start manual calibration until you see the
message on the display and follow the instructions on screen� Enter the flow rates for each
zone if asked to do so�
3
In the ‘Adjust the supply vents’ step, select the duct with the highest flow rate and
resistance and, using a pressure-compensated air flow meter, measure the flow rate at
this vent� If the flow rate is too high or too low, you can adjust it using the arrow keys on
the DucoBox Energy Comfort (Plus)� Depending on the user controller version, this can
also be done by pressing the (lower) and (higher) buttons on a paired user controller�
Adjust the flow rate so as to obtain the desired flow rate at this vent� The flow rate can be
fine adjusted at the vent�
NOTE
: The system needs around ten seconds to run stably when adjusting the flow rate
using the buttons on the DucoBox Energy Comfort (Plus), the User controller or making
large changes at the vent. The system will indicate when the calibration is stable. The
flow rate cannot be measured correctly until after this time has elapsed.
/
/
4
Proceed now with the remaining supply vents� The flow rate from these other vents
must only be adjusted at the vents themselves. Adjusting vents will not alter the flow of
previously calibrated vents�
5
When all supply valves are adjusted, press the enter button ( ) on the DucoBox Energy
Comfort (Plus) or you can confirm by long pressing the AUTO button of the control switch�
Calibrating
exhaust
vents
6
Repeat steps
3
to
5
inclusive for all exhaust vents�