27
ENGLISH
L2003212 Installation guide for DucoBox Energy Comfort (Plus) (Revision A | 18.10.2022)
08.C
Checking
The calibrated flow rates can be checked at the various vents once adjustment and calibration have been completed� Do this by
going into advanced mode (see page 31) and select “
CALIBRATION
→
VERIFY HIGH LEVEL
”� The DucoBox Energy Comfort (Plus)
will now ventilate for 30 minutes at its calibrated ventilation setting�
08.D
Copying calibration data in case of serial construction
The DucoBox Energy Comfort (Plus) contains the 'Calib by Code’ function in order to copy the calibration data to another unit� This
is useful in projects with identical residential units and installations� In this case, only a single unit needs to run through the cali-
bration procedure� The other unit will take over the calibration settings of the first unit by copying the calibration code�
Copying the calibration data to another unit
1
Make sure that all valves are adjusted identically (pres fine-tuning) for each installation�
2
Activate advanced mode:
• Scroll down to
ADVANCED
and press enter�
• Enter the installer’s code
9876
and press enter�
3
On the calibrated unit, navigate to
CALIBRATION
→
CALIB BY CODE
→
GET CODE
and write down this code�
4
On the units to be calibrated, navigate to
CALIBRATION
→
CALIB BY CODE
→
ENTER CODE
and enter the code�
5
The unit will indicate when the calibration is completed� This can take a few
minutes� If the unit does not succeed in completing the calibration (e�g�, due to a
wrong code or differences in the installation), the user can cancel the calibration
by simultaneously pressing the two arrow keys�
DUCO recommends to check the calibrated flow rates after the calibration (see page26)�