12
ENGLISH
L2003212 Installation guide for DucoBox Energy Comfort (Plus) (Revision A | 18.10.2022)
04.D
Options power supply
For power supply, DUCO offers two options:
DESCRIPTION
ARTICLE NUMBER
Power supply 230VAC-24VDC/20W + housing
0000-4763
Duco Wired power adapter 230VAC-24VDC/20W
0000-4762
04.E
RF (wireless communication)
RF components have a maximum free-field range of 350 metres� This distance will be much less in a building because of obstacles�
Therefore, you will need to take objects such as walls, concrete and metal into account� All slave components (except those which
are battery powered) also act as repeaters� Signals from components that are unable to make a (strong) connection with the master
component are forwarded automatically via no more than one other non-battery-powered component (= hop)� Please refer to infor-
mation sheet RF communication (L8000018) at www�duco�eu for further information�
DUCO RF
Power Supply
230 VAC
Wiring
1,5 mm²
Frequency
868,3 MHz
Maximum distance
350 m, free field (less through obstacles)
Maximum number of components
Up to 25 wireless components in a single system
04.F
Wired (cabled communication)
Wired components can be daisy-chained (= recommended)� This means that a separate cable will not be required for each compo-
nent� A single central power supply can be used�
The cable required is a 0�75 mm² data cable� We strongly recommend using a shielded cable to avoid interfering with data commu-
nication�
DUCO WIRED
Power Supply
24 VDC
Wiring
5 x 0�75 mm² (5 x 0�25 mm² from Tronic window ventilators)
Maximum distance
up to 300 m
Maximum number of components
Up to 50 wired components in a single system
04.G
ModBus TCP/IP
Communication with building management systems is possible, for reading out information as well as controlling the ventilation
system� This requires the DucoBox Energy Comfort (Plus) to be equipped with an optional Communication Print WIFI� Consult the
ModBus TCP/IP instructions at www�duco�eu�
04.H
Perilex
The Perilex variants of DucoBox Energy Comfort (Plus) can be controlled via a wired controller with Perilex connection� Please
consult the manual 'Quick-Start Perilex plug' via the DUCO website�