22
ENGLISH
L2003212 Installation guide for DucoBox Energy Comfort (Plus) (Revision A | 18.10.2022)
07
Electrical installation
07.A
Pairing components
Pairing control components with the DucoBox Energy Comfort (Plus)
1
Activate advanced mode:
• Scroll down to
ADVANCED
and press enter�
• Enter the installer’s code
9876
and press enter�
2
Go to the
INSTALLATION
menu�
3
Start the
WIZARD
�
4
Was the supply divided into zones via iAV valves?
1� If YES -> go to step 5
2� If NO -> go to step 6
5
Register the multi-zone valves by briefly pressing the 'INST' button of the respec-
tive zone valves�
IMPORTANT: Remember the order of sign-up� This determines the order of the
zones! The first valve logged on is zone 1, the next is zone 2 … with a maximum of
4 zones�
6
Pair the desired control components with the system� I�e�:
a) DucoBox Energy Comfort (Plus) without zone control: all components
b) DucoBox Energy Comfort (Plus) with zone control: only the components in the
wet rooms (bathroom, toilet, kitchen, laundry room, …)
Briefly tap any button of all components to be paired*� The LED on the component
will start flashing green once it has been paired correctly� The number of paired
components will be shown on the display menu� Confirm by pressing enter ( )
once all the desired components have been paired�
* Please refer to the control component manual for comprehensive instructions�
Without zone control:
With zone control:
7
Only with zoned system:
For example, each zone can be (part of) the day zone (living room, office, …) or
(part of) the night zone (bedrooms)�
a) Pair the desired control components with zone 1� Then confirm by pressing
enter ( )�
b) Pair the desired control components with zone 2� Then confirm by pressing
enter ( )�
c) Only when 3 zones were defined: pair the desired control components to zone
3� Then confirm by pressing enter ( )�
d) Only when 4 zones were defined: pair the desired control components to zone
4� Then confirm by pressing enter ( )�
All components have now been paired� This wizard can be run again if additional control components need to be paired at a later
stage� All previously paired components will be retained in the network�