Air-side calibration
Calibrating the DucoBox Eco can be split into various steps:
1� Pre-setting exhaust vents
2� Calibrating flow rates
The system needs to be configured for it to work correctly.
This will ensure its operation is as quiet as possible and energy-efficient.
08.A
Pre-setting vents
The exhaust vents are installed in a duct for moisture-laden/stale air extraction� In order to calibrate the air extraction correctly,
these vents must be set depending on the situation in accordance with the table below�
SITUATION 1
:
One vent per zone
SITUATION 2
:
Multiple vents per zone
with
equal flow rates
SITUATION 3
:
Multiple vents per valve with
different flow rates
Set all vents to the fully
open position, regardless of
the desired flow rate� When
using DucoVent Design
exhaust vents, leave the ou-
ter ring in place for acoustic
effect�
Set all vents to the fully
open position, regardless of
the desired flow rate� With
DucoVent Design vents, turn
the cone on the trim plate to
the fully open position�
Set the vents so they match the desired flow rate in accordance
with the table�
DUCOVENT
DESIGN
DUCOVENT BASIC
AND OTHER VENTS
75 m3/h
100%
open
50 m3/h
50%
open
25 m3/h
25%
open
+