L2000012 Installation guide for DucoBox Eco (Revision E.1 | 13.05.2020)
09
Water side calibration
09.A
Venting the circuit
09.B
Setting flow rate
The water flow rate can be set via the display (standard setting is 430 l/h) in line with the chosen concept�
Venting circuit
1
Turn off the tap for the incoming cold circulating
water connection (RET)�
2
Open the vent caps by unscrewing them�
3
Using the display, select
CALIBRATION
→
WATER
CIRCUIT
→
CIRCUIT VENTING
and press enter�
4
Take care to ensure that pipe pressure remains con-
stant while venting!
5
Open the tap for the incoming cold circulating water
connection (RET) again after 1 minute�
6
Wait until the venting procedure has finished�
7
Repeat the procedure if necessary�