64
C.4 Inspection of Electric Cables
Electric cables run between the charge regulator and the solar array, the batteries,
and the refrigerator. These cables should be inspected every time you visit an
installation to make sure that they are in good condition.
(a)
Check the connections on the cables, which go to the battery terminals, the
solar array terminals, the refrigerator terminals (on the compressor controller
and on the refrigerator socket), and the charges regulator terminals strip. The
connections should be clean and tight. If they are loose, tighten them. If they
are dirty, take them off and clean them with a wire brush before connecting
them tightly.
(b)
Follow each cable to its end, wherever possible. Look for the following types
of damage: the cable has been cut, the insulation is worn or the insulation has
been eaten away leaving the metal inside showing.
(c)
If the cable is damaged, it must be replaced. Follow the instructions on page
83 to replace the cable.
(d)
If there is evidence of animals eating the cables it may be necessary to use
armored cable.
Summary of Contents for VC150
Page 1: ......
Page 3: ...3 SECTION I ...
Page 4: ...4 ...
Page 24: ...24 MODULE AND BATTERY WIRING DIAGRAMS SYSTEM WIRING DIAGRAM ...
Page 25: ...25 SYSTEM WIRING DIAGRAM GENERAL LAYOUT DIAGRAM ...
Page 26: ...26 GENERAL LAYOUT DIAGRAM ELECTRICAL CIRCUIT DIAGRAM ...
Page 27: ...27 ELECTRICAL CIRCUIT DIAGRAM REFRIGERATION CIRCUIT DIAGRAM ...
Page 28: ...28 REFRIGERATION CIRCUIT DIAGRAM ...
Page 29: ...29 SECTION II ...
Page 38: ...38 ...
Page 39: ...39 ...
Page 42: ...42 ...
Page 44: ...44 ...
Page 50: ...50 ...
Page 124: ...124 ANNEX 1 COMPONENT LAYOUTS OF SOME COMMONLY USED SOLAR REFRIGERATOR ...
Page 125: ...125 ...
Page 126: ...126 ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...129 ...
Page 130: ...130 ANNEX II ADDITIONAL EPI TOOL KIT NEEDED FOR PHOTOVOLTAIC REFRIGERATOR REPAIR ...
Page 136: ...136 ...
Page 137: ...137 ...